NonStop NS2200 Series Planning Guide

Total (BTU/hour)Unit Heat (BTU/hour)
Maximum
Unit Heat (BTU/hour)
Typical
Number InstalledEnclosure Type
539437DL380p Gen8
Networking CLIM, 3
copper ports/2 optical
ports (IP or Telco)
427256
M8381-25 SAS disk
enclosure (no disks)
3017SAS 2.5 in. 10k rpm
disk drive
2414SAS 2.5 in. 15k rpm
disk drive
20.520.5200GB SAS 2.5”
SSD, Gen1
20.520.5200GB SAS 2.5”
SSD, Gen2
6868Maintenance switch
(Ethernet)
1
601601Rack-mount system
console (NSCR4)
392358Rack-mount system
console (NSCR210 or
NSCR212)
9696Rack-mount keyboard
and display
1
Maintenance switch has only one plug. If a UPS is installed in the modular cabinet, the maintenance switch plug must
be connected to the extension bar on the left side of the modular cabinet.
Operating Temperature, Humidity, and Altitude
Maximum Rate of Change
per Hour
Recommended Range
1
Operating Range
1
Specification
50° to 95° F (10° to 35° C)Temperature (rack-mounted
system console and
maintenance switch)
18° F (10° C) Repetitive68° to 77° F (20° to 25° C)
36° F (20° C) Nonrepetitive
-50° to 95° F (10° to 35° C)Temperature (CLIMs, SAS
disk enclosure, blade
elements)
1.8° F (1° C) Repetitive
5.4° F (3° C) Nonrepetitive
6%, noncondensing40% to 50%,
noncondensing
20% to 80%,
noncondensing
Humidity
--0 to 10,000 feet (0 to
3,000 meters)
Altitude
2
1
Operating and recommended ranges refer to the ambient air temperature and humidity measured 19.7 in. (50 cm) from
the front of the air intake cooling vents.
2
For each 1000 feet (305 m) increase in altitude above 10,000 feet (up to a maximum of 15,000 feet), subtract 1.
F (0.83× C) from the upper limit of the operating and recommended temperature ranges.
Environmental Specifications 85