NonStop NS2400 Series Planning Guide

ValueSpecification
894 BTU/hourTypical heat dissipation
1112 BTU/hourMaximum heat dissipation
NS2400T CLIM Specifications
DL380p Gen8 CLIM T CG ValueDL380 G6 CLIM T CG ValueSpecification
Enclosure Dimensions
2 U2 UU Height
3.4 in (8.6 cm)3.4 in (8.6 cm)Height
17.5 in (44.5 cm)17.5 in (44.5 cm)Width
27.3 in (69.2 cm)27.3 in (69.2 cm)Depth
Enclosure Weight
63 lbs (28.6 kg)62 lbs (28 kg)Unboxed
Power and Heat
22Number of power inputs
130 W234 WTypical power consumption
160 W240 WMaximum power consumption
444 BTU/hour798 BTU/hourTypical heat dissipation
870 BTU/hour1051BTU/hourMaximum heat dissipation
CLIM Ground Connections
All DC-powered CLIMs have a ground plate that is mounted on the back of the enclosure. The
ground plate provides one threaded stud for the ground cable lug. The other end of the ground
cable connects to the cabinet grounding rail.
In addition, there is a ground cable in the unterminated end of DC input power cable that connects
from the power supply to the fuse panel or breaker panel. The ground cable in this cable must also
connect to the cabinet grounding rail. Ask your HP service provider to refer to the CLuster I/O
Module (CLIM) Installation and Configuration Guide for detailed information about connecting
these ground cables.
M8391-24T and M8392-24T SAS Disk Enclosure Specifications
M8391-24T and M8392-24T ValueSpecification
Enclosure Dimensions
2 UU Height
3.5 in (8.9 cm)Height
17.6 in (44.7 cm)Width
20.28 in (51.5 cm)Depth
Enclosure Weight
47 lbs (21 kg)Unboxed, empty of disk drives
Power and Heat