NonStop NS2400 Series Planning Guide

ValueSpecification
1.7 in (4.32 cm)Height
17 in (43.2 cm)Width
9 in (22.9 cm)Depth
Enclosure Weight
5 lbs (2.3 kg)Unboxed
Power and Heat
2Number of power inputs
35 WTypical power consumption
40 WMaximum power consumption
119 BTU/hourTypical heat dissipation
136 BTU/hourMaximum heat dissipation
CG Maintenance Switch Ground Connections
The CG maintenance switch has a threaded post located to the right of the DC input terminal block.
A ground cable connects from this grounding post to the nearest cabinet grounding rail. For detailed
information about connecting the ground cables, ask your HP service provider to refer to the
NonStop NS2200 Series and NS2400 Series Hardware Installation Manual.
Data Cables
The enclosures in this system are suitable for connection to intrabuilding or non-exposed wiring or
cabling only. Unshielded, twisted-pair (UTP) cables may be used for both NEBS™ and non-NEBS
installations.
Cabinet and Enclosure Weights Worksheet
The total weight of each cabinet is the sum the weight of the cabinet plus each enclosure installed
in it. All weights are approximate. Use this worksheet in Table 8 (page 134) to calculate the weight.
Table 7 Rack Weight Worksheet for NonStop NS2400T
Weight Worksheet for Rack Number _____
TotalWeight
Number of
EnclosuresEnclosure Type kglbkglb
29.966Blade Element
7.316Fuse panel
28.262VIO Enclosure
2862CLIM T CG
8.619CG CLIM patch panel
2147SAS Disk Enclosure (no
disks)
0.51Disk drives in disk enclosures
10.924160 DAT unit
25CG Maintenance switch
------Total Payload
Data Cables 133