NonStop NS2400 Series Planning Guide

Table 12 Example of Completed Weight Worksheet for Sample NS2400ST System Rack Number
1 (continued)
Weight Worksheet for Rack Number __1___
TotalWeight
Number of
EnclosuresEnclosure Type kglbkglb
220485220485Seismic rack R2, 36U
1, 2
5161139------Total Weight
1
Maximum payload weight for the 36U cabinet: 1200 lbs (544.3 kg)
2
Cross out seismic rack that does not apply.
Heat Dissipation Worksheet for Seismic Racks
To calculate the heat dissipation for each seismic rack, use the worksheet in Table 13 (page 144).
Table 13 Heat Dissipation Worksheet for Seismic Racks
Heat Dissipation Worksheet for Rack Number ______
Total (BTU/hour)
Maximum Unit Heat (BTU/hour with
both lines powered)
Number
InstalledEnclosure Type
239 x (fuse panel load /160)
2
Fuse panel
1
1212Blade Element (16 GB)
1240Blade Element (32 GB)
1268Blade Element (48 GB)
1112VIO enclosure
1051DL380 G6 CLIM CG
546DL380p Gen8 CLIM CG
614M8391-24CG and
M8392-24CG Disk
Enclosure
31Disk drive 10k rpm
24Disk drive 15k rpm
20.5
200GB SAS 2.5” SSD,
Gen1
20.5200GB SAS 2.5” SSD,
Gen2
51160 DAT unit
137CG Maintenance switch
----Total Heat (BTU/hour)
1
Maximum value. Assumes full load per side of 70W.
2
Fuse panel load is the total nominal current on both sides
144 Specifications for NonStop NS2400ST Systems