NonStop NS2400 Series Planning Guide

Power Load Worksheet, NS2400ST Seismic Rack
Enclosures in Seismic Racks
Power and current specifications for seismic racks are the sum of the power and current specifications
for each enclosure that are installed in the cabinet. Use the worksheet in Table 14 (page 145) to
calculate the power load for each rack and to indicate the breaker panel and fuse panel
configurations.
Table 14 Seismic Rack Power Load Worksheet
Power Load Worksheet for Rack Number ______
Fuse Size
Fuse Panel
2
SubtotalWatts per EnclosureNumber of Enclosures
Enclosure Type
1
----355Blade Element (16 GB)
----364Blade Element (32 GB)
372Blade Element (48 GB)
326VIO Enclosure
308DL380 G6 CLIM CG
3
160DL380p Gen8 CLIM
CG
180M8391-24CG and
M8392-24CG Disk
Enclosure (no disks)
4, 4
9Disk drive 10k rpm
7Disk drive 15k rpm
6
200GB SAS 2.5” SSD,
Gen1
6
200GB SAS 2.5” SSD,
Gen2
30DAT Tape
5
40Maintenance Switch
--------Total
1
Cross out components that don't apply.
2
Fuse panels have a maximum of 4 TPA fuses and 5 GMT fuses.
3
For the CLIM, choose a fuse panel with a 15A GMT or TPA fuse.
4
For disk enclosures, choose a fuse panel with a 30A TPA fuse.
5
Choose fuse panel with GMT fuse.
Power Load Worksheet, NS2400ST Seismic Rack 145