NonStop NS2400 Series Planning Guide
Ethernet Cables
Ethernet connections for a dedicated service LAN require CAT 5e or CAT 6 unshielded twisted-pair
(UTP) cables.
SWAN Concentrator Restrictions
NOTE: SWAN and SWAN 2 concentrators are only supported on the NonStop NS2400
commercial system. SWAN/SWAN 2 concentrators can be connected to an IP CLIM or the 10/100
Ethernet ports on a VIO enclosure with these restrictions:
• Isolate any ServerNet wide area networks (SWANs) on the system. The system must be
equipped with at least two LANs: one LAN for SWAN/SWAN 2 concentrators and one for
the dedicated service LAN.
• Most SWANs are configured redundantly using two or more subnets. Those subnets also must
be isolated from the dedicated service LAN.
• Do not connect SWANs on a subnet containing a DHCP.
Dedicated Service LAN Links
You can implement up-system service LAN connectivity using:
• “Dedicated Service LAN Links With Two VIO Enclosures” (page 158)
• “Dedicated Service LAN Links With IP CLIMs” (page 158)
• “Dedicated Service LAN Links With Telco CLIMs” (page 159)
Dedicated Service LAN Links With Two VIO Enclosures
You can implement up-system service LAN connectivity using the Ethernet ports on two VIO
enclosures. The values in this table show the identification for the Ethernet ports in slot 6B, port A
of both VIO enclosure modules (module 2 and module 3) and connected to the maintenance switch:
IP ConfigurationTCP/IP StackEthernet LIFEthernet PIFGMS for Ethernet Port
Location in VIO
Enclosure
IP: 192.168.36.10$ZTCP0L1002RG10026.0.A100.2.6b Port A
Subnet: %FFFF0000
Hostname: osmlanx
IP: 192.168.36.11G$ZTCP1L1003RG10036.0.A100.3.6b Port A
Subnet: %FFFF0000
Hostname: osmlany
Dedicated Service LAN Links With IP CLIMs
You can implement up-system service LAN connectivity using IP CLIMs, if the system has at least
two IP CLIMs. The values in this table show the identification for the IP CLIMs in a NonStop NS2400
series system and connected to the maintenance switch. For example, in this table an IP CLIM
named N100241 is connected to slot 4, port 1 of the VIO enclosure located in group 100, module
2.
IP ConfigurationTCP/IP StackGMS for IP CLIM Location in VIO
Enclosure
IP: 192.168.36.10$ZTCP0100.2.4.1
Subnet:
%hFFFFFF00
158 Maintenance and Support Connectivity