NonStop NS2400 Series Planning Guide
• “Branch Circuits and Circuit Breakers, Three-Phase PDUs” (page 187)
• “Circuit Breaker Ratings for Three-Phase UPS” (page 187)
Single-Phase Power Specifications in G2 Racks
North America and Japan: 200 to 240V AC, Monitored Single-Phase PDU Power
The NonStop NS2400 cabinet can contain two monitored power distribution units (PDUs). The
PDU power characteristics are:
PDU input characteristics
• 200 to 240 V AC, single-phase, 40A RMS, 3-wire
• 50/60Hz
• 6.5 feet (2 m) attached power cord
• Non-NEMA Locking CS8265C, 50A input plug as
shown below:
PDU output characteristics
• 3 circuit-breaker-protected 20A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
International: 200 to 240V AC, Monitored Single-Phase PDU Power
The NonStop NS2400 cabinet can contain two monitored power distribution units (PDUs). The
PDU power characteristics are:
PDU input characteristics
• 200 to 240 V AC, single-phase, 32A RMS, 3-wire
• 50/60Hz
• 6.5 feet (2 m) attached harmonized power cord
• IEC309 332P6 3-pin, 32A input plug as shown below:
PDU output characteristics
• 3 circuit-breaker-protected 20A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 12A receptacle type
AC Input Power for Modular Cabinets in G2 Racks 183