NonStop NS2400 Series Planning Guide
Branch Circuits and Circuit Breakers, Modular Single-Phase PDUs
In NonStop NS2400 cabinets without the optional rack-mounted UPS, each of the two PDUs
requires a separate branch circuit of these ratings:
Amps (see following “CAUTION”)Volts (Phase-to-Phase)Region
50200 to 240North America and Japan
CAUTION: Be sure the hardware configuration and resultant power loads of each cabinet within
the system do not exceed the capacity of the branch circuit according to applicable electrical codes
and regulations.
Select circuit breaker ratings according to local codes and any applicable regulations for the circuit
capacity. Note that circuit breaker ratings vary if your system includes the optional rack-mounted
HP Model R5000 Integrated UPS.
Circuit Breaker Ratings for Single-Phase UPS
These ratings apply to NonStop NS2400 series systems with the optional rack-mounted HP Model
R5000 Integrated UPS which is used for a single-phase power configuration:
UPS Input Rating
1
Input PlugPower Out
(VA/Watts)
Operating Voltage
Settings
Version
Dedicated 30 AmpL6-30P5000/4500200/208
2
, 220,
230, 240
North America and
Japan
Dedicated 32 AmpIEC-309 32 Amp5000/4500200, 208, 220,
230
3
, 240
International
1
The UPS input requires a dedicated (unshared) branch circuit that is suitably rated for your specific UPS.
2
Factory-default setting
3
Factory-default setting
For further information and specifications on the single-phase UPS, refer to the HP UPS R5000 User
Guide at:
http://h20000.www2.hp.com/bc/docs/support/SupportManual/c02945229/c02945229.pdf
AC Input Power for Modular Cabinets in G2 Racks 185