Three-Phase Power Specifications in G2 Racks
North America and Japan: 200 to 240V AC, Three-Phase PDU Power
The NonStop NS2400 includes two power distribution units (PDUs). The PDU power characteristics
are:
PDU input characteristics
200V to 240V AC, 3-phase delta, 24A RMS, 4-wire
50/60Hz
6.5 feet (2 m) attached power cord
NEMA L15-30P input plug as shown below:
PDU output characteristics
3 circuit-breaker-protected 13.86A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
International: 380 to 415V AC, Three-Phase PDU Power
The NonStop NS2400 cabinet includes two power distribution units (PDUs). The PDU power
characteristics are:
PDU input characteristics
380 to 415 V AC, 3-phase Wye, 16A RMS, 5-wire
6.5 feet (2 m) attached harmonized power cord
50/60Hz
IEC309 516P6 5-pin, 16A input plug as shown below:
PDU output characteristics
3 circuit-breaker-protected 16A load segments
36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type