NonStop NS2400 Series Planning Guide
Three-Phase Power Specifications in G2 Racks
North America and Japan: 200 to 240V AC, Three-Phase PDU Power
The NonStop NS2400 includes two power distribution units (PDUs). The PDU power characteristics
are:
PDU input characteristics
• 200V to 240V AC, 3-phase delta, 24A RMS, 4-wire
• 50/60Hz
• 6.5 feet (2 m) attached power cord
• NEMA L15-30P input plug as shown below:
PDU output characteristics
• 3 circuit-breaker-protected 13.86A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
International: 380 to 415V AC, Three-Phase PDU Power
The NonStop NS2400 cabinet includes two power distribution units (PDUs). The PDU power
characteristics are:
PDU input characteristics
• 380 to 415 V AC, 3-phase Wye, 16A RMS, 5-wire
• 6.5 feet (2 m) attached harmonized power cord
• 50/60Hz
• IEC309 516P6 5-pin, 16A input plug as shown below:
PDU output characteristics
• 3 circuit-breaker-protected 16A load segments
• 36 AC receptacles per PDU (12 per segment) - IEC 320
C13 10A receptacle type
• 3 AC receptacles per PDU (1 per segment) - IEC 320
C19 16A receptacle type
186 Power Configurations for NonStop NS2400 Series Systems in G2 Racks