NonStop NS2400 Series Planning Guide
NonStop System With Data Center UPS, Both Power Rails
In this non-supported configuration, a NonStop system is installed in a Tier-I, Tier-II or Tier-III data
center. The data center tier classification is defined by the Uptime InstituteTM Tier Classifications
Define Site Infrastructure White Paper.
IMPORTANT: If this configuration is used, there is no guarantee that your data center will never
lose power.
Figure 60 shows an example of a non-supported configuration in a NonStop system with the left
and right PDUs connected to the data center UPS. In this configuration, OSM does not manage or
monitor the data center UPS.
Figure 60 NonStop System With Data Center UPS, Both Power Rails
Non-Supported UPS Configurations 195










