NonStop NS2400 Series Planning Guide
TotalWeightNumber of
Enclosures
Enclosure Type
kglbskglbs
12.738rack-mount system
console, keyboard,
and display
57126R5000 UPS
(single-phase)
139.2 (with
batteries)
307 (with
batteries)
R12000/3 UPS
(three-phase)
59.8 (without
batteries)
135 (without
batteries)
77170ERM for three-phase
power (AF434A)
63139R5000 ERM for
single-phase power
----Total
1
Modular cabinet weight includes the PDUs and their associated wiring and receptacles.
2
Maximum payload weight for the 36U G2 rack cabinet: 1200 lbs (544.3 kg).
3
Maximum payload weight for the 42U G2 rack cabinet: 1200 lbs (544.3 kg).
4
Maximum payload weight for the 36U Intelligent rack cabinet: 3000 lbs (1360 kg).
5
Maximum payload weight for the 42U Intelligent rack cabinet: 3000 lbs (1360 kg).
6
iPDU=Intelligent PDU
7
mPDU=Modular PDU
For examples of calculating the weight for various enclosure combinations, see “Calculating
Specifications for Enclosure Combinations” (page 82).
Modular Cabinet Stability
Cabinet stabilizers are required when you have less than four cabinets bayed together.
NOTE: Cabinet stability is of special concern when equipment is routinely installed, removed,
or accessed within the cabinet. Stability is addressed through the use of leveling feet, baying kits
or baying plates, fixed stabilizers, and/or ballast.
Use baying kits to bay G2 racks to G2 racks of the same height or Intelligent racks to Intelligent
racks of the same height. Use baying plates to bay Intelligent racks to G2 racks of the same height.
In all cases, a rack cannot be bayed with another rack of a different height.
For information about best practices for cabinets, your HP service provider can consult:
• HP 10000 G2 Series Rack User Guide
• Best practices for HP 10000 Series and HP 10000 G2 Series Racks
• HP Intelligent Rack Family User Guide
• HP Intelligent Rack Family Options Installation Guide
Modular Cabinet Stability 79