Replacing an AC Power Cord in a Power Shelf
Notes for Replacing an AC Power Cord in a
Power Shelf
The AC receptacles into which the server is connected must be accessible to the
operator. Alternatively, the branch circuit breaker supplying power to each
receptacle must be accessible to the operator and plainly marked so as to
indicate that the circuit breaker is for this receptacle.
●
Some AC power cords contain faulty connectors that when touched, vibrated, or
flexed can cause intermittent power or the loss of a processor to occur. If the
power cord molding is elliptical rather than square, or if the power cord part
number is TPN 064583, you must replace the power cord offline with power cord
TPN 421575. For more information, refer to FCO36048.
●
The end of the AC power cord is caged in a holder that holds it in place for
mating to the power supply. If the wrong AC power cord is installed, the power
supply might push it back out of place without making a connection.
●