Site Preparation Guide - HP Integrity rx1620
System Specifications
Dimensions and Weights
Chapter 2
12
Dimensions and Weights
This section provides dimensions and weights of hp Integrity rx1620 Server components.
Component Dimensions
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor is to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.
Electrical Specifications
This section provides electrical specifications for the system.
Circuit Breaker
The marked electrical for the HP Server is 8 amps. The recommended circuit breaker size is > 8 amps per line
cord for North America. For countries outside North America, consult the local electrical authority that has
jurisdiction for the recommended circuit breaker size.
Table 2-2 Server Component Dimensions
Dimension Value
Height-Inches (Centimeters) 1.75 (4.5)
Width-Inches (Centimeters) 17.32 (44)
Depth-Inches (Centimeters) 21.5 (54.6)
Weight-Pounds (Kilograms) Unloaded 26 (9.7)
Fully loaded <32 (13.4)