Site Preparation Guide - HP Integrity rx1620
System Specifications
Environmental Specifications
Chapter 2
15
Typical System Configurations
The system configurations shown in Table 2-6, Typical Configuration Power Consumption Values, are typical
of most systems and show the power and cooling values required for the listed components. These power and
cooling values are considered typical and not maximum for the configurations shown.
Environmental Specifications
This section provides the temperature/humidity requirements, noise emission, and air flow specifications for
the HP Server.
Temperature and Humidity
Ambient intake air temperature is often different from ambient room temperature; you should measure the
operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just
checking ambient room conditions.
Operating Environment
The system is designed to run continuously and meet reliability goals in an ambient temperature of 5° C-35°
C at sea level. The maximum allowable temperature is derated 1° C per 1,000 feet of elevation above 5,000
feet above sea level up to 30° C at 10,000 feet. For optimum reliability and per formance, the recommended
operating range is 20° C to 25° C and 40%-50% relative humidity.
Table 2-6 Typical Configuration Power Consumption Values
CPU
Qty
Memory
Gigabytes
PCI Cards
(assuming
10W each)
DVDs
Hard
Disk
Drives
Bulk
Power
Supplies
Typical
AC
Source
Power
Typical
Cooling-
BTU/Hr
1 512 MB
(2 DIMMs @
256 MB ea.
0 0 1 1 190W 600
1 16 GB
(8 DIMMs @
2 GB ea.
2 1 2 1 324W 1021
2 512 MB
(2 DIMMs @
256 MB ea.
0 0 1 1 268W 844
2 16 GB
(8 DIMMs @
2 GB ea.
2 1 2 1 460W 1266