hp workstations zx6000, hp server rx2600 - operation and maintenance guide
Event, Error and Warning Messages
Sensor Data Record Repository (SDRR)
Appendix D
216
Cooling Unit Status SDRs (Sensors 0x11-0x14)
This sensor reports the state of the redundant cooling units.
Events:
Field Name Value Notes
SDR Type 0x02 Compact sensor record
Entity ID 0x1E Cooling unit
Entity Instance 0x01-0x03
Sensor Initialization 0x00 Sensor events+scanning disabled at BMC reset
Sensor Capabilities 0x40 Ignore sensor = no
Auto-rearm = yes
Hysteresis = none
Thresholds = none
Event Message Control support = entire sensor
only (01)
Sensor Type 0x0A Cooling device
Event/Reading Type Code 0x07 Discrete – severity
Assertion Event Mask 0x0007 0x00: transition to OK
0x01: transition to non-critical from OK
0x02: transition to critical from less severe
Deassertion Event Mask 0x0000
Discrete Reading Mask 0x0007
String “Cooling 1 (Sys)”
“Cooling 2 (Mem)”
“Cooling 3 (I/O)”
Triplet Event
0A:07:00 Cooling unit OK
0A:07:01 Cooling unit warning
0A:07:02 Cooling unit fault requiring system shutdown