Site Preparation Guide. First Edition - HP Integrity rx2620 Server (August 2006)
System Specifications
Grounding
Chapter 1
14
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor is to be connected from the unit to the building installation earth or, if supplied by a separately
derived system, at the supply transformer or motor-generator set grounding point.
Electrical Specifications
This section provides electrical specifications for the your HP Server.
System Power Specifications
Available power (output) is the maximum DC power that the power supply can supply to the system.
Maximum input power is what the power supply requires from the AC line to deliver that maximum DC
output (given worst case efficiency and max loading)
Maximum input current is the worst case/highest current given the lowest input voltage and the maximum
input power
Table 1-3 System Power Specifications
Parameter Total Rating
Peak
(15 sec.)
Max. per
PCI-X
Sockets
64-bit,
133MHz
Input voltage 100-120 VAC 200-240 VAC N/A N/A
Input current (max) 7.2 A 3.2 A N/A N/A
Input frequency 50 to 60 Hz 50 to 60 Hz N/A N/A
Maximum AC input power 714 W (2438 BTU) N/A N/A
Power supply maximum output
power
600 W (2049 BTU) N/A 85 W total for
PCI sockets
Max current at +12 V 49 A N/A 0.5 A
Max current at -12 V 0.35 A N/A 0.1 A
Max current at +3.3 V 34 A N/A 4.6 A
Max current at +5 V 18 A 31 A 3 A
Max current at +3.3 V standby 3.5 A N/A N/A