HP Integrity rx2660 Server User Service Guide

Installing a Hot–Swappable Power Supply
The Data Center server has at least one hot-swappable power supply installed before shipping.
This power supply is located at the rear of the server. You can install a second, optional power
supply to provide 1+1 capability.
NOTE: If you have an Office Friendly server, you have two power supplies already installed.
You do not need to perform this procedure.
CAUTION: Observe all ESD safety precautions before attempting this procedure. Failure to follow
ESD safety precautions can result in damage to the server.
NOTE: The power supply is a hot-swappable device. It does not require interaction with the
operating system before the it is removed from or installed into the server.
Power Supply Loading Guidelines
The supported configuration of the server requires a minimum of one power supply installed in slot
P1. The right slot (viewed from the rear of the server) is slot P1, and the left slot is P2.
Figure 14 Power Supply Location
21
Power supply 2Power supply 1
CAUTION: If you do not purchase a second power supply, the empty power supply slot must
remain covered with the supplied metal filler panel. Failure to observe this caution can result in
server shutdown due to overheating.
Installing a Power Supply
To install a power supply:
1. Remove the metal slot filler by pulling it straight out of the server using the finger holes (1).
Installing Additional Components 45