Site Preparation Guide, Third Edition - HP Integrity rx2660 Server

Dimensions and Weight
Table 1-2 lists the dimensions and weight of the HP Integrity rx2660 Data Center server and the
rx2660 Office Friendly server for a rack- or pedestal-mounted configuration.
Table 1-2 Rack- or Pedestal-Mounted Server Dimensions
ValueDimensions and Weight
Data Center Server Dimensions
67.3 cm (26.5 in) Depth
48.3 cm (19 in) Width
8.6 cm (3.4 in) Height
Minimum configuration 21 kg (46 lb)
Maximum configuration 28 kg (61 lb)
Data Center Server Weight
2URack unit
Office Friendly Server Dimensions
69.0 cm (27.18 in) Depth
27.6 cm (10.88 in) w/feet
12.7 cm (5 in) w/o feet
Width
50.8 cm (20 in) Height
Minimum configuration 30 kg (66 lb)
Maximum configuration 37 kg (81 lb)
Office Friendly Server Weight
Grounding
The site building shall provide a safety ground/protective earth for each ac service entrance to
all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor is to be connected from the unit to the building installation earth
or, if supplied by a separately derived system, at the supply transformer or motor-generator set
grounding point.
Electrical Specifications
This section provides electrical specifications for the server.
System Power Specifications
Available power (output) is the maximum dc power that the power supply can supply to the
system.
Maximum input power is what the power supply requires from the ac line to deliver that
maximum dc output (given worst case efficiency and maximum loading).
Maximum input current is the worst case/highest current given the lowest input voltage and the
maximum input power.
12 Server Specifications