Site Preparation Guide, Third Edition - HP Integrity rx2660 Server

Table 1-3 System Power Specifications
Total RatingParameter
200-240 VAC100-127 VAC100 VACInput voltage
7 A10 A10 AMarked input current
6.7 A10 A10 AInput current (maximum)
47 to 63 Hz47 to 63 Hz47 to 63 HzInput frequency
1205 W1000 W1000 WMaximum ac input power
1000 W850 W800 WPower supply maximum output power
82 A69 A65 AMax current at +12 V
0.3 A0.3 A0.3 AMax current at -12 V
8 A8 A8 AMax current at +3.3 V standby
2 A2 A2 AMax current at +5 V standby
If an overload triggers the power supply overload protection, the system is immediately powered
off. To reset the power supply unit, follow these steps:
1. Disconnect the power cord.
2. Determine what caused the overload by contacting an HP support representative.
3. Reconnect the power cord.
4. Reboot the system.
NOTE: If an overload occurs twice, there is an undetected short circuit somewhere.
When you use the front panel power button to turn off the server, power consumption falls
below the low power consumption, but doesn't reach zero. To reach zero power consumption
in “off mode, either unplug the server or use a power block with a switch.
Power Consumption and Cooling
The power consumptions listed in Table 1-4 are valid for a standard configuration as shipped
(one 1.4 GHz dual-core processor, 1 GB of memory, one 1000 W power supply, one internal hard
disk drive, and one internal DVD-RW drive).
All information in this section is based on primary power consumptions with one power supply
installed.
Table 1-4 Additional Component Power Consumption
Power ConsumptionAdditional Component
443.6 Btu/h130 WProcessor
78.4 Btu/h23 WSAS disk drive (with I/O access)
54.5 Btu/h16 WSAS disk (idle)
34.12 Btu/h to 85.30 Btu/h10 to 25 WPCIe/PCI-X card
Physical and Environmental Specifications
This section provides the temperature and humidity requirements, noise emission, and air flow
specifications for the server.
Physical and Environmental Specifications 13