Site Preparation Guide, Third Edition - HP Integrity rx2660 Server

Table 1-6 Physical and Environmental Specifications for the Data Center Server
Server DimensionsWeightCondition
Maximum
Airflow @
35 degrees
C
1
Nominal
Airflow
Typical Heat
Release
PedestalRackPedestalRackServer200-240
VAC
100-127
VAC
D 69 cm W 27.6
cm (with feet) W
12.7 cm (w/o
feet) H 50.8 (D
27.2 in W 10.8 in
(with feet) W 5.0
in (w/o feet) H
20.0 in)
D 67.3
cm W
48.3 cm
H 8.6 cm
(D 26.5
in W 19
in H 3.4
in)
30 kg -
37 kg
(66 lb -
81 lb)
25 kg
- 32
kg
(55
lb -
70
lb)
21 kg -
28 kg (46
lb - 61
lb)
m3/hrCFMm3/hrCFMWattsWatts
19011210461363 W363 WMinimum
Config.
19011213479782 W782 WMaximum
Config.
19011210461483 W483 WTypical
Config.
Two 4 GB DDR2 DIMMs, n o PCIe/PCI-X public cards
or, RAID card on private I/O slot.
Min
config
Airflow cooling scheme (front to rear)ASHRAE
Class 1
Eight 4 GB DDR2 DIMMs, three PCIe/PCI-X cards on
public I/O slots, and RAID card in private slot.
Max
Config
Four 4 GB DDR2 DIMMs, one PCIe/PCI-X card on
public I/O slots, and RAID card in private slot.
Typical
Config
1 Derate maximum dry bulb temperature 1 degree / 300 meters above 900 meters.
Table 1-7 (page 16) shows the physical and environmental specifications for the Office Friendly
server.
Physical and Environmental Specifications 15