System Backplane Power Board Fault. Probable Cause: A DC-DC converter on the
named power board failed. Recommended Action: Contact HP Support personnel
to troubleshoot the problem Caution: The 1.8 volt converters are N+1. The 3.3 volt
converters are N+2. If there is a situation where a 1.8 fails at the same time as a 3.3
on a different power board, replace the failed 1.8 board first. WBEM EventID: 686.
WBEM ProviderName: FPL_IndicationProvider.Warning7858
Read of EEPROM failed. Probable Cause: The I2C controller on the Utilities Board
(CLU section) is bad. This will be shown by many I2C failure codes in the Error Log.
These codes should identify entities on both the System Backplane and the Master
IO Backplane. Recommended Action: Contact HP Support personnel to troubleshoot
the problem. WBEM EventID: 687. WBEM ProviderName: FPL_IndicationProvider.Warning7863
Read of EEPROM failed. Probable Cause: The I2C controller on the Utilities Board
(CLU section) is bad. This will be shown by many I2C failure codes in the Error Log.
These codes should identify entities on both the System Backplane and the Master
IO Backplane. Recommended Action: Contact HP Support personnel to troubleshoot
the problem. WBEM EventID: 688. WBEM ProviderName: FPL_IndicationProvider.Warning7864
Read of LPM Fault failed. Probable Cause: The I2C controller on the Utilities Board
(CLU section) is bad. This will be shown by many I2C failure codes in the Error Log.
These codes should identify entities on both the System Backplane and the Master
IO Backplane. Recommended Action: Contact HP Support personnel to troubleshoot
the problem. WBEM EventID: 689. WBEM ProviderName: FPL_IndicationProvider.Warning7865
IO Power Board Over temperature. Probable Cause: The ambient air is too warm.
Recommended Action: Check the Error Log for other Overtemp Warnings to confirm
the environmental problem. WBEM EventID: 690. WBEM ProviderName:
FPL_IndicationProvider.Error7866
IO Power Board Fault. Probable Cause: Input power has created some fault conditions.
This will be evident by the presence of several chassis codes in the Error Log within
the same time frame. Recommended Action: The Error Log must be reviewed carefully
for the root cause of the errors. There is almost always a single cause, even if many
events are reported. WBEM EventID: 691. WBEM ProviderName:
FPL_IndicationProvider.Error7867
Voltage Margin on IO Power Board failed. Probable Cause: The MP is not
communicating with the CLU. Recommended Action: The MP bus (USB) is not
functioning. There should be many entries in the Error Log with the same type of
error message. They will point to MP bus errors. Also, try the GSP 'PS' command.
This will display status of entities within a cabinet. WBEM EventID: 692. WBEM
ProviderName: FPL_IndicationProvider.Warning7871
Failure to read data from a SBCH FRUID EEPROM. Probable Cause: The CLU cannot
read the data contained in the EEPROM on the SBCH board in the same cabinet.
Recommended Action: Contact HP Support personnel to troubleshoot the problem.
If this is the only READ failure in this timeframe, replace the SBCH board following
the SBCH Board Remove + Replace Procedures as soon as possible. If there are other
READ failures in this same cabinet, replace the Utilities Board following the Utilities
Board Remove and Replace Procedures. WBEM EventID: 694. WBEM ProviderName:
FPL_IndicationProvider.Warning7873
Failure to read data from a UGUY FRUID EEPROM. Probable Cause: Attempted
access to read the UGUY FRUID EEPROM failed. Recommended Action: If there is
only one FRUID that can't be read, replace that FRU as soon as possible. If there are
a lot of log entries for different FRUs, suspect the Utilities Board or the Utilities cable
to those FRUs. For example, if the failures are all associated with a Master IO
Backplane, the failing FRU is probably the Utilities cable to that backplane. WBEM
EventID: 695. WBEM ProviderName: FPL_IndicationProvider.Warning7874
Read EEPROM failed. Probable Cause: The I2C controller on the Utilities Board (CLU
section) is bad. This will be shown by many I2C failure codes in the Error Log. These
codes should identify entities on both the System Backplane and the Master IO
Backplane. Recommended Action: Replace the Utilities board (UGUY) following the
Utilities Board Remove and Replace procedures. WBEM EventID: 696. WBEM
ProviderName: FPL_IndicationProvider.Warning7875