HP Integrity rx2800 i2 Server User Service Guide

Table 4 System power specifications (continued)
Parameter
+12VSB /2.5A MAX+12VSB /2.5A MAX+12VSB /2.5A MAX
If an overload triggers the power supply overload protection, the system is immediately powered
off. To reset the power supply unit:
1. Disconnect the power cord.
2. Determine what caused the overload by contacting an HP support representative.
3. Reconnect the power cord.
4. Reboot the system.
NOTE: If an overload occurs twice, an undetected short circuit exists.
When you use the front panel power button to turn off the server, power consumption falls below
the low power consumption, but does not reach zero. To reach zero power consumption in "off"
mode, either unplug the server or use a power block with a switch.
Power consumption and cooling
The power consumptions listed in Table 5 (page 17) are valid for a standard configuration as
shipped.
All information in this section is based on primary power consumptions with one power supply
installed.
Table 5 Standard configuration power consumption
Power consumptionStandard configuration
1228 Btu/h (maximum)360 W (maximum)One 1.46 GHz quad-core processor, 4 GB memory,
one 1200 W power supply, and one SAS disk drive
Table 6 Additional component power consumption
Power consumptionAdditional component
443.6 Btu/h130 WProcessor
78.4 Btu/h23 WSAS disk drive (with I/O access)
54.5 Btu/h16 WSAS disk (idle)
34.12 Btu/h to 85.30 Btu/h10 to 25 WPCIe card
Server physical and environmental specifications
Operating temperature and humidity ranges might vary, depending on the installed mass storage
devices. High humidity levels can cause improper disk operation. Low humidity levels can aggravate
static electricity issues and cause excessive wear of the disk surface.
NOTE: De-rate maximum dry bulb temperature 1°/300 m (1000 ft) above 900 m (3000 ft).
Table 7 Environmental specifications (system processing unit with hard disk)
Value
Parameter
Office Friendly ServerData Center Server
+5° C to +35° C (+41° F to +95° F)Operating temperature (up to 1524 m/5000 ft)
1
- 40° C to +70° C (40° F to 158° F)Non-operating temperature
Server physical and environmental specifications 17