HP Integrity rx3600 Site Preparation Guide Regulatory Model Number: RSVLA-0404 HP Part Number: AB463-9005C Published: November 2007 Edition:
Legal Notices ©Copyright 2007 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Printed in U.S.A.
Table of Contents About This Document ........................................................................................................7 Intended Audience.................................................................................................................................7 New and Changed Information in This Edition.....................................................................................7 Publishing History........................................................................
List of Tables 1 1-1 1-2 1-3 1-4 1-5 1-6 Publishing History Details..............................................................................................................7 Server Specifications........................................................................................................................9 Rack- or Pedestal-Installed Server Dimensions and Values..........................................................10 System Power Specifications.............................................
About This Document This document describes how to prepare your site for installation of your HP Integrity rx3600 server, Regulatory Model Number: RSVLA-0404. The document printing date and part number indicate the document’s current edition. The printing date will change when a new edition is printed. Minor changes may be made at reprint without changing the printing date. The document part number will change when extensive changes are made.
Bold Term ComputerOut UserInput Command Variable [] {} ... | Text that is strongly emphasized. The defined use of an important word or phrase. Text displayed by the computer. Commands and other text that you type. A command name or qualified command phrase. The name of a variable that you may replace in a command or function or information in a display that represents several possible values. The contents are optional in formats and command descriptions.
1 System Specifications This chapter provides the system specifications for the HP Integrity rx3600 server. This chapter addresses the following topics: • • • • • “Server Specifications” (page 9) “Dimensions and Values” (page 10) “Grounding” (page 10) “Electrical Specifications” (page 10) “Physical and Environmental Specifications” (page 11) Server Specifications Table 1-1 lists the server specifications for the HP Integrity rx3600.
Dimensions and Values Table 1-2 lists the dimensions and values of the HP Integrity rx3600 for a rack- or pedestal-installed configuration . Table 1-2 Rack- or Pedestal-Installed Server Dimensions and Values Dimension Value Server weight (loaded product weight range estimate) 34-40.8 kg (75-90 lbs.) Rack Rack dimensions (depth x width x height) 69.6 cm (27.4 in.) x 44 cm (17.32 in.) x 17.24 cm (6.8 in.) Rack weight Max: 45.36 kg. (100 lbs.
Table 1-3 System Power Specifications (continued) Parameter Rating Maximum per PCI/PCI-X/PCIe Socket 25 W per socket 25 W per socket 2 1095 W (3736 BTU/hr) 1056 W (3603 BTU/hr) 3 Minimum Configuration 432 W (1474 BTU/hr) 422 W (1439 BTU/hr) Typical Configuration4 685 W (2337 BTU/hr) 669 W (2283 BTU/hr) Maximum Configuration 1 2 3 4 The infrastructure should be sized such that any single power supply can safely provide all the power required by the system.
Table 1-5 Environmental Specifications (system processing unit with hard disk) Parameter Value Operating temperature +5˚ C to +35˚ C (+41˚ F to +95˚ F) Storage temperature - 40˚ C to +70˚ C (-40˚ F to +158˚ F) Over-temperature shutdown +40˚ C (+104˚ F) Operating humidity 15% to 80% relative (noncondensing) Storage humidity 90% relative (noncondensing) at + 65˚ C Acoustic Noise Emission (ISO 9296) Sound Power Level1 LwAd =7.3B Sound Pressure Level LpAm =57.
1 2 Derate maximum dry bulb temperature 1oC/300 m above 900 m. m3/hr=1.
Glossary A-B Apparent power A value of power for AC circuits that is calculated as the product of RMS current times RMS voltage, without taking the power factor into account. ASHRAE Standard 52-76 Industry standard for air filtration efficiency set forth by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASL Above sea level. board A printed circuit assembly (PCA). Also called a card or adapter. Btu/h The abbreviation for British thermal units.
cables. The FCC (Federal Communications Commission) regulates a portion of this problem through Part 15 of their rules and regulations. Even more stringent than the FCC Part 15 requirements, Network Equipment Building Standards (NEBS) covers a large range of requirements including criteria for personnel safety, protection of property, and operational continuity.
Index D dimensions, server, 10 E electrical specifications, 10 S specifications, server, 9 W weight server, 9, 10 17