Installation Guide, Seventh Edition - HP Integrity rx4640 Server

Installing Additional Components
Accessing a Pedestal-Mounted Server
Chapter 3
31
Extend the Server from the Rack
NOTE Ensure that there is enough area (approximately 1.5 meters [4.5 ft.]) to fully extend the server
out the front and work on it.
To extend the server from the rack, perform the following steps:
Step 1. Remove the T-25 screws that fasten the server to the rack.
Step 2. Flip out the two pull handles at either end of the front bezel and slowly pull the unit forward by the
handles. The server is fully extended when the rail clips are locked in place. After your server is
fully extended, the front and top covers are accessible.
Insert the Server into the Rack
To insert the server into the rack, perform the following steps:
Step 1. Press the rail clips on either side of the server inward and push the server into the rack until it
stops.
Step 2. Replace the T-25 screws that fasten the server to the rack.
Accessing a Pedestal-Mounted Server
The HP Integrity rx4640 server is also designed to be pedestal mounted. You do not need to remove the
pedestal from the HP server to gain access to internal components. The front bezel, front cover, and top cover
may be removed with the pedestal attached to the HP server.
WARNING Ensure that the HP server is properly grounded when performing remove and
replace procedures. Use an antistatic wrist strap and grounding mat similar to those
found in the HP Electrically Conductive Field Service Kit.