Site Preparation Guide HP Integrity rx4640 Server Regulatory Model Number: RSVLA-0201 Manufacturing Part Number: A6961-96015 Second Edition August 2006 U.S.A. © Copyright 2006 Hewlett-Packard Development Company, L.P.
Legal Notices Copyright Notices. © Copyright 2006 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Printed in the USA.
Contents About This Document Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . New and Changed Information in This Edition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Publishing History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Document Organization. . . . . . . . . .
Contents Space Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Delivery Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operational Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Floor Plan Grid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figures Figure 1-1. hp Integrity rx4640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-2. Airflow through hp Integrity rx4640 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-1. Raised Floor Metal Strip Ground System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 2-2. Delivery Survey (Part 1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figures 6
About This Document This document provides information and instructions on installing the HP Integrity rx4640 server into a standard rack-mounted configuration. The document printing date and part number indicate the document’s current edition. The printing date changes when a new edition is printed. Minor changes may be made at reprint without changing the printing date. The document part number changes when extensive changes are made.
Typographic Conventions This document uses the following conventions. WARNING A warning lists requirements that you must meet to avoid personal injury. CAUTION A caution provides information required to avoid losing data or avoid losing server functionality. NOTE A note highlights useful information such as restrictions, recommendations, or important details about HP product features. Book Title The title of a book.
Table 2 HP-UX 11i Releases (Continued) Release Identifier B.11.23 Release Name HP-UX 11i v2.0 Supported Processor Architecture Intel Itanium Related Documents You can find other information on HP server hardware management, Microsoft® Windows®, and diagnostic support tools in the following publications. Web Site for HP Technical Documentation: http://docs.hp.com Server Hardware Information: http://docs.hp.
1 System Specifications System Configuration The following table lists the minimum and maximum configurations for an hp Integrity rx4640 server.
System Specifications Dimensions and Weights Dimensions and Weights This section provides dimensions and weights of hp Integrity rx4640 server components. Component Dimensions Table 1-2 Rack Mounted Server Component Dimensions Dimension Value Height- Centimeters (Inches) 17.3 cm (6.8 in.) Width- Centimeters (Inches) 48.2 cm (19 in.) Depth- Centimeters (Inches) 69.0 cm (27.2 in.) Weight- Kilograms (Pounds) Unloaded 40 kg (88 lb.) Fully loaded 45.4 kg (100 lb.
System Specifications Electrical Specifications System AC Power Specifications Power Cords Table 2-3lists the various power cables available for use with the hp Integrity rx4640 system. Table 1-3 Part Number Power Cords Description Country 8120-5341 Pwr Crd C15/S Africa 2.5m BLACK CA ASSY 917 S. Africa 8120-1351 Pwr Crd C13/BS-1363 2.3m BLACK CA ASSY 900 UK & HK & Singapore 8120-1369 Pwr Crd C13/AS-3112 2.0m GRAY CA ASSY 901 Australia 8120-1689 Pwr Crd C13/CEE 7 2.
System Specifications Electrical Specifications System Power Specifications Tables 2-4 and 2-5list the AC power requirements for the server. These tables provide information to help determine the amount of AC power needed for your computer room.
System Specifications Electrical Specifications Typical System Configurations The system configurations shown in Table 1-6, Typical Configuration Power Consumption Values, are typical of most systems and show the power and cooling values required for the listed components. These power and cooling values are considered typical and not maximum for the configurations shown.
System Specifications Environmental Specifications Environmental Specifications This section provides the temperature/humidity requirements, noise emission, and air flow specifications for the HP Server. Temperature and Humidity Ambient intake air temperature is often different from ambient room temperature; you should measure the operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just checking ambient room conditions.
System Specifications Environmental Specifications NOTE A power supply filler is required in the unused power supply slot to maintain proper airflow throughout the system. PCI/Mass Storage Section Cooling Four 127 mm fans located in the center of the chassis provide airflow for all of the PCI slots. The fans are controlled by the system temperature and run at the speed necessary to maintain proper internal temperature throughout the chassis.
System Specifications Environmental Specifications 18 Chapter 1
2 General Site Preparation Guidelines The following information provides general principles and practices to consider before the installation or operation of an hp Integrity rx4640 server. Electrical Factors NOTE Electrical practices and suggestions in this guide are based on North American practices. For regions and areas outside North America, local electrical codes will take precedence over North American electrical codes.
General Site Preparation Guidelines Electrical Factors Most computer room installations are equipped with the following fire protection devices: • Smoke detectors • Fire and temperature alarms • Fire extinguishing system Additional safety devices are: • Circuit breakers • An emergency power cutoff switch • Devices specific to the geographic location for example, earthquake protection Lighting Requirements for Equipment Servicing Adequate lighting and utility outlets in a computer room reduce the
General Site Preparation Guidelines Electrical Factors Sources of Voltage Fluctuations Voltage fluctuations, sometimes called glitches, affect the quality of electrical power.
General Site Preparation Guidelines Electrical Factors Power System Protection The hp Integrity rx4640 server can be protected from the sources of many of these electrical disturbances by using: • A dedicated power distribution system • Power conditioning equipment • Over- and under-voltage detection and protection circuits • Screening to cancel out the effects of undesirable transmissions • Lightning arresters on power cables to protect equipment against electrical storms Precautions have been ta
General Site Preparation Guidelines Electrical Factors Grounding Systems IT Power System This product has not been evaluated for connection to an IT power system (an AC distribution system having no direct connection to earth according to IEC 60950).
General Site Preparation Guidelines Electrical Factors Dual power sources might originate from two different transformers or two different UPS devices. Voltage potentials from ground pin to ground pin of these sources should be measured and verified to be at or near 0.0 volts. Voltage levels that deviate or are measured above 3.0 volts should be further investigated. Increased voltages might be hazardous to personnel, and should be further investigated.
General Site Preparation Guidelines Electrical Factors Raised Floor “High Frequency Noise” Grounding If a raised floor system is used, install a complete signal grounding grid for maintaining equal potential over a broad band of frequencies. The grounding grid should be connected to the equipment cabinet and electrical service entrance ground at multiple connection points using a minimum #6 AWG (16mm2) wire ground conductor. The following figure illustrates a metallic strip grounding system.
General Site Preparation Guidelines Electrical Factors Figure 2-1 26 Raised Floor Metal Strip Ground System Chapter 2
General Site Preparation Guidelines Electrical Factors Equipment Grounding Implementation Details Connect all HP equipment cabinets to the site ground grid as follows: Step 1. Attach one end of each ground strap to the applicable cabinet ground lug. Step 2. Attach the other end to the nearest pedestal base (raised floor) or cable trough ground point (nonraised floor). Step 3. Check that the braid contact on each end of the ground strap consists of a terminal and connection hardware (a 1/4-in. [6.
General Site Preparation Guidelines Environmental Elements Environmental Elements The following environmental elements can affect an hp Integrity rx4640 server installation: • Computer room preparation • Cooling requirements • Humidity level • Air conditioning ducts • Dust and pollution control • Electrostatic discharge (ESD) prevention • Acoustics (noise reduction) Computer Room Preparation The following guidelines are recommended when preparing a computer room for an hp Integrity rx4640 ser
General Site Preparation Guidelines Environmental Elements • Reheating • Air distribution • System controls adequate to maintain the computer room within specified operating ranges Lighting and personnel must also be included. For example, a person dissipates about 450 BTUs per hour while performing a typical computer room task.
General Site Preparation Guidelines Environmental Elements Perforated floor panels (available from the raised floor manufacturer) should be located around the front of the system cabinets. Supply air emitted though the perforated floor panels is then available near the cooling air intake vents of the hp Integrity rx4640 server cabinets.
General Site Preparation Guidelines Environmental Elements Specifically, disk drives, tape drives, and some other mechanical devices can have bearing failures resulting from airborne abrasive particles. Dust may also blanket electronic components like printed circuit boards, causing premature failure due to excess heat and/or humidity build up on the boards. Other failures to power supplies and other electronic components can be caused by metallically conductive particles, including zinc whiskers.
General Site Preparation Guidelines Environmental Elements Electrostatic Discharge (ESD) Prevention Static charges (voltage levels) occur when objects are separated or rubbed together.
General Site Preparation Guidelines Facility Characteristics Facility Characteristics This section contains information about facility characteristics that must be considered for the installation or operation of an hp Integrity rx4640 server.
General Site Preparation Guidelines Facility Characteristics Table 2-2 Floor Loading Term Definitions (Continued) Term Definition Concentrated load The load that a floor panel can support on a 1-in2 (6.45 cm2) area at the panel’s weakest point (typically the center of the panel), without the surface of the panel deflecting more than a predetermined amount. Ultimate load The maximum load (per floor panel) that the floor system can support without failure.
General Site Preparation Guidelines Facility Characteristics Table 2-3 Typical Raised Floor Specifications (Continued) Itema Average floor load Rating 500 lb (227 kg) a. From Table 2-2 on page 33 b. With 0.08 in (0.2 cm) of span maximum deflection Windows Avoid housing computers in a room with windows. Sunlight entering a computer room may cause problems. Magnetic tape storage media is damaged if exposed to direct sunlight.
General Site Preparation Guidelines Space Requirements Space Requirements This section contains information about space requirements for an hp Integrity rx4640 server. This data should be used as the basic guideline for space plan developments. Other factors, such as airflow, lighting, and equipment space requirements must also be considered. Delivery Space Requirements There should be enough clearance to move equipment safely from the receiving area to the computer room.
General Site Preparation Guidelines Space Requirements • Equipment cable routing Chapter 2 37
General Site Preparation Guidelines Conversion Factors and Formulas Conversion Factors and Formulas The conversion factors provided here are intended to ease data calculation for systems that do not conform specifically to the configurations listed in this Site Preparation Guide. Listed below are the conversion factors used in this document, as well as additional conversion factors which may be helpful in determining those factors required for site planning. Conversion Factors • Refrigeration — 1 watt =.
General Site Preparation Guidelines Sample of an Installation Schedule Sample of an Installation Schedule The following schedule lists the sequence of events for a typical system installation: • 60 days before installation — Floor plan design completed and mailed to Hewlett-Packard (if required to be an HP task) • 30 days before installation — Primary power and air conditioning installation completed — Telephone and data cables installed — Fire protection equipment installed — Major facility changes com
General Site Preparation Guidelines Sample Site Inspection Checklist Sample Site Inspection Checklist Table 2-4 Customer and Hewlett-Packard Information Customer Information Name: Phone No: Street Address: City or Town: State or Province: Country Zip or postal code: Primary customer contact: Phone No.: Secondary customer contact: Phone No.: Traffic coordinator: Phone No.
General Site Preparation Guidelines Sample Site Inspection Checklist Table 2-5 Site Inspection Checklist (Continued) Please check either Yes or No. If No, include comment# or date 9. Is a telephone line available? 10. Are customer supplied peripheral cables and LAN cables available and of the proper type? 11. Are floor tiles in good condition and properly braced? 12. Is floor tile underside shiny or painted? If painted, judge the need for particulate test. Comment or Date Power and lighting No.
General Site Preparation Guidelines Sample Site Inspection Checklist Table 2-5 Site Inspection Checklist (Continued) Please check either Yes or No. If No, include comment# or date No. Area or condition 27. Can cooling be maintained between 20° C and 55° C (up to 5,000 ft.)? Derate 1° C/1,000 ft. above 5,000 ft. and up to 10,000 ft. 28. Can temperature changes be held to 10° C per hour with tape media? Can temperature changes be held to 20° C per hour without tape media? 29.
General Site Preparation Guidelines Delivery Survey Delivery Survey The delivery survey forms list delivery or installation requirements. If any of the items on the list apply, enter the appropriate information in the areas provided on the form. Special instructions or recommendations should be entered on the special instructions or recommendations form.
General Site Preparation Guidelines Delivery Survey Figure 2-2 Delivery Survey (Part 1) ELEVATOR Fill in the following information if an elevator is required to move equipment. Capacity (lb or kg) ________________ Depth ________________ Height ________________ Width ________________ Height Depth Width STAIRS Please list number of flights and stairway dimensions.
General Site Preparation Guidelines Delivery Survey Figure 2-3 Delivery Survey (Part 2) DELIVERY CHECKLIST DOCK DELIVERY Is dock large enough for a semitrailer? Yes ___________ No ___________ Circle the location of the dock and give street name if different than address. North West East South STREET DELIVERY Circle the location of access door and list street name if different than address. North West East South List height ___________ and width ___________ of access door.
General Site Preparation Guidelines Delivery Survey 46 Chapter 2
Glossary A-B Apparent power A value of power for AC circuits that is calculated as the product of RMS current times RMS voltage, without taking the power factor into account. ASHRAE Standard 52-76 Industry standard for air filtration efficiency set forth by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASL Above sea level. board A printed circuit assembly (PCA). Also called a card or adapter. Btu/h The abbreviation for British thermal units.
Glossary PCA operational continuity. The documents cover both physical requirements including: Space Planning, Temperature, Humidity, Fire, Earthquake, Vibration, Transportation, Acoustical, Air Quality and Illumination; and electrical criteria including: Electrostatic Discharge (ESD), Electromagnetic Interference (EMI), Lightning and AC Power Fault, Steady State Power Induction, Corrosion, DC Potential Difference, Electrical Safety and Bonding and Grounding.
Index A air conditioning system recommendations, 29 air conditioning ducts, 30 air distribution system room space return air, 29 operational space requirements, 36 typical raised floor site, 34 windows, 35 fire protection, 19 floor loading raised floor, 33 B basic air conditioning equipment requirements, 28 basic air distribution systems, 29 G grounding systems, 23 electrical conduit ground, 23 C circuit breaker, 12 computer room safety fire protection, 19 cooling requirements, 28 H humidity level, 30