Site Preparation Guide, Second Edition - HP Integrity rx4640 Server
System Specifications
Electrical Specifications
Chapter 1
14
System Power Specifications
Tables 2-4 and 2-5list the AC power requirements for the server. These tables provide information to help
determine the amount of AC power needed for your computer room.
Table 1-4 System Power Specifications
Specification Value
Nominal input voltage 200 - 240 (VAC RMS)
Minimum Operating Voltage 180 VAC
Maximum Operating Voltage 264 VAC
Frequency range (minimum -
maximum)
50-60 Hz
Number of phases 1
Maximum input current 8 A RMS
Maximum inrush current 100A (peak), 55A (average) 0msec- 1msec
55A (peak), 33A (average) 1msec - 2msec
55A (peak), 22A (average) 2msec -10sec
25A (peak), 15A (average) 10msec - 150msec
Dropout carry through time at
minimum line voltage
20 ms
Power factor correction > 0.95 At all loads of 90%-100% of supply rating
> 0.75 At all loads of 50% - 90% of supply rating
Ground leakage current <1.1mA per line cord
Table 1-5 System Power Requirements
Power Required (50-60Hz) Watts VA Comments
Maximum configuration
a
a. Maximum power is the sum of the worst case power consumption values of every subsystem in your
hp Integrity rx4640. These worst case values should be used to calculate the worst case power
consumption for your facility installation.
1368 1440 Maximum Theoretical
Typical configuration
b
b. Typical power consumption values were measured while running power intensive applications.
These values are generally lower than maximum power numbers because all the subsystems in
your HP Server rarely draw maximum power simultaneously and for long durations.
1065 1125 Typical