HP Integrity rx6600 Site Preparation Guide Regulatory Model Number: RSVLA-0405 HP Part Number: AB464-9005C Published: November 2007 Edition:
© Copyright 2007 Hewlett-Packard Development Company, L.P Legal Notices The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. Printed in U.S.A.
Table of Contents About This Document ........................................................................................................7 Intended Audience.................................................................................................................................7 New and Changed Information in This Edition.....................................................................................7 Publishing History........................................................................
List of Tables 1 1-1 1-2 1-3 1-4 1-5 1-6 Publishing History Details..............................................................................................................7 Server Specifications........................................................................................................................9 Rack- or Pedestal-Installed Server Dimensions and Values..........................................................10 System Power Specifications.............................................
About This Document This document describes how to prepare your site for installation of your HP Integrity rx6600 server, Regulatory Model Number: RSVLA-0405. The document printing date and part number indicate the document’s current edition. The printing date will change when a new edition is printed. Minor changes may be made at reprint without changing the printing date. The document part number will change when extensive changes are made.
Bold Bold ComputerOut UserInput Command Variable [] {} ... Text that is strongly emphasized. The defined use of an important word or phrase. Text displayed by the computer. Commands and other text that you type. A command name or qualified command phrase. The name of a variable that you may replace in a command or function or information in a display that represents several possible values. The contents are optional in formats and command descriptions.
1 System Specifications Server Specifications Table 1-1 lists the server specifications for the HP Integrity rx6600. Table 1-1 Server Specifications Component Specification rx6600 with PCI/PCI-X IOBP rx6600 with PCI/PCI-X/PCIe IOBP Processors One, two, three, or four Itanium dual-core processors: • 1.4 GHz / 12 MB cache • 1.6 GHz / 18 MB cache • 1.6 GHz / 24 MB cache • 1.42 GHz / 12 MB • 1.6 GHz / 18 MB • 1.
Table 1-2 Rack- or Pedestal-Installed Server Dimensions and Values Dimension Value Server weight (loaded product weight range estimate) 53.4 - 68 kg (120-150 lbs.) Rack Rack dimensions (depth x width x height) 69.6 cm (27.4 in) x 44 cm (17.32 in) x 30.58 cm (12.04 in) Rack weight Max: 68.04 kg (150 lbs) Rack unit Server takes up 7U in the rack Pedestal Pedestal dimensions (depth x width x height) 69.3 cm (27.3 in) x 48.9 cm (19.3 in) x 42.2 cm (16.7 in) Pedestal weight Max: 15.5 kg. (34 lbs.
Table 1-3 System Power Specifications (continued) Parameter Rating Minimum Configuration3 443 W (1512 BTU) Typical Configuration4 998 W (3407 BTU) 1 2 3 4 The infrastructure should be sized such that any single power supply can safely provide all the power required by the system. Maximum theoretical configuration: (4x) 1.6G/24M CPUs, (48x) 4GB DDRII DIMM memory, (16x) SAS Hard Drives, (8x) PCI/PCI-X/PCI-E added to public I/O cards. Minimum possible configuration: (1x) Itanium 1.4G/12M or 1.
Table 1-5 Environmental Specifications (system processing unit with hard disk) (continued) Parameter Value Operating humidity 15% to 80% relative (noncondensing) Storage humidity 90% relative (noncondensing) at + 65˚ C Acoustic Noise Emission (ISO 9296) Sound Power Level1 LwAd =7.5 B Sound Pressure Level LpAm =57.5 dB Altitude Operating altitude 0 to 3000 m (10,000 ft.) max Storage altitude 0 to 4572 m (15,000 ft.) max 1 Typical configuration at room temperature (25˚C).
Glossary A-B Apparent power A value of power for ac circuits that is calculated as the product of RMS current times RMS voltage, without taking the power factor into account. ASHRAE Standard 52-76 Industry standard for air filtration efficiency set forth by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. ASL Above sea level. board A printed circuit assembly (PCA). Also called a card or adapter. Btu/h The abbreviation for British thermal units.
cables. The FCC (Federal Communications Commission) regulates a portion of this problem through Part 15 of their rules and regulations. Even more stringent than the FCC Part 15 requirements, Network Equipment Building Standards (NEBS) covers a large range of requirements including criteria for personnel safety, protection of property, and operational continuity.
Index A altitude operating, 11 storage, 12 D dimensions server, 9, 10, 11 dimensions and weights, 9 dimensions, server, 9, 10, 11 W weight server, 9 weight, server, 9 15