HP Insight Manager WBEM Provider Events Reference

Event DescriptionEvent SeverityEvent ID
An error encountered while retrieving the expected neighbor fabric chip for
distributing traffic over crossbar links. Probable Cause: Unexpected error retrieving
information from the fabric graph. Recommended Action: Collect IPMI event logs
and contact your HP Support Representative to investigate the fabric system firmware
subsystem WBEM EventID: 5189. WBEM ProviderName: FPL_IndicationProviderWarning12025
Could not read crossbar neighbor information during routing. Probable Cause: System
Firmware encountered an error while reading a fabric crossbar chip. Recommended
Action: Collect IPMI Event Logs and contact your HP Service Representative to
investigate the fabric subsystem. WBEM EventID: 5190. WBEM ProviderName:
FPL_IndicationProviderWarning12028
Could not establish route for local crossbar during route around routing. Probable
Cause: System Firmware could not establish routing from the local crossbar that
would be needed to complete the route around routing. Recommended Action:
Collect IPMI Event Logs and contact your HP Support Representative to investigate
the fabric subsystem. WBEM EventID: 5191. WBEM ProviderName:
FPL_IndicationProviderWarning12029
An invalid or non-supported TPM (Trusted Platform Module) has been detected.
Ensure that the TPM is fully seated into the system board and verify the operating
system is TPM capable. Probable Cause: An invalid, non supported TPM is being
used in the system Recommended Action: Contact HP for support WBEM EventID:
5193. WBEM ProviderName: FPL_IndicationProviderError12047
Invalid or unsupported TPM detected in the system. TPM is disabled. Probable Cause:
An invalid or unsupported TPM has been detected in the system. TPM is disabled.
Recommended Action: Contact HP support WBEM EventID: 5194. WBEM
ProviderName: FPL_IndicationProviderWarning12048
TPM failed initialization. Security features disabled. Probable Cause: Bad TPM chip
Recommended Action: contact HP support WBEM EventID: 5195. WBEM
ProviderName: FPL_IndicationProviderWarning12049
A CPU module's temperature has exceed the high temperature threshold or a CPU
power module fault has occurred. As a result of this event, the CPU has been inhibited.
The Cell must be powered off then on using the MP's PE command to clear. Probable
Cause: A CPU module's temperature has exceed the high temperature threshold or
a CPU power module fault has occurred. Recommended Action: Contact HP support
personnel to troubleshoot the problem. WBEM EventID: 5192. WBEM ProviderName:
FPL_IndicationProviderError12050
SFW detected an error while writing to stable store flash. Probable Cause: Cosmic
radiation Bad flash part Recommended Action: Reboot, if problem persists, contact
HP support WBEM EventID: 6861. WBEM ProviderName: FPL_IndicationProviderWarning12069
PCI interlock open with PCI power applied. Probable Cause: PCI interlock has been
opened with PCI slot power on. Recommended Action: power down slot attempting
to remove PCI card. WBEM EventID: 5230. WBEM ProviderName:
FPL_IndicationProviderWarning12091
Fault detected on low drop out regulator on I/O backplane. Probable Cause: A
defective component could cause this fault. Recommended Action: Check the
backplane. WBEM EventID: 5237. WBEM ProviderName: FPL_IndicationProviderError12101
Fault detected on low drop out regulator on main backplane. Probable Cause: The
specified low dropout regulator on the main backplane is reporting a fault.
Recommended Action: Check the main backplane. WBEM EventID: 5238. WBEM
ProviderName: FPL_IndicationProviderError12102
Fault detected hot swap controller of specified core IO. Probable Cause: The hot swap
controller for the specified core IO is reporting fault. Recommended Action: Check
the specified core IO. WBEM EventID: 5250. WBEM ProviderName:
FPL_IndicationProviderError12103
Platform Events 95