General Site Preparation Guidelines
Facility Characteristics
43
Facility Characteristics
This section contains information about facility characteristics that must be considered for the installation or
operation of the server. Facility characteristics are:
• Floor loading
•Windows
• Altitude effects
Floor Loading
The computer room floor must be able to support the total weight of the installed computer system as well as
the weight of the individual cabinets as they are moved into position.
Floor loading is usually not an issue in nonraised floor installations. The information presented in this
section is directed toward raised floor installations.
NOTE Any floor system under consideration for a server installation should be verified by an
appropriate floor system consultant.
Raised Floor Loading
Raised floor loading is a function of the manufacturer’s load specification and the positioning of the
equipment relative to the raised floor grid. Though HP cannot assume responsibility for determining the
suitability of a particular raised floor system, it does provide information and illustrations for the customer or
local agencies to determine installation requirements.
The following guidelines are recommended:
• Because many raised floor systems do not have grid stringers between floor stands, the lateral support for
the floor stands depends on adjacent panels being in place. To avoid compromising this type of floor
system while gaining under floor access, remove only one floor panel at a time.
• Larger floor grids (bigger panels) are generally rated for lighter loads.
CAUTION Do not install any raised floor system until you have carefully examined it to verify that it is
adequate to support the appropriate installation.
Floor Loading Terms
Table B-3 defines floor loading terms.
Table B-3 Floor Loading Term Definitions
Term Definition
Dead load The weight of the raised panel floor system, including the
understructure. Expressed in lb/ft
2
(kg/m
2
).