Site Preparation Guide, Fourth Editon - HP Integrity rx7620 Server
Appendix B
General Site Preparation Guidelines
Facility Characteristics
45
Windows
Avoid housing computers in a room with windows. Sunlight entering a computer room can cause problems.
Magnetic tape storage media is damaged if exposed to direct sunlight. Also, the heat generated by sunlight
places an additional load on the cooling system.
Concentrated load
b
1250 lb (567 kg)
Ultimate load 4000 lb (1814 kg) per
panel
Rolling load 400 lb (181 kg)
Average floor load 500 lb (227 kg)
a. From Table B-3 on page 43
b. With 0.08 in. (0.2 cm) of span maximum deflection
Table B-4 Typical Raised Floor Specifications (Continued)
Item
a
Rating