HP Insight Management WBEM Provider Events Reference Guide

AC power to the PDCA was removed. Data Byte 3 specifies PDCA number. Probable
Cause: Circuit breakers on the PDCA are open. Recommended Action: Close the
PDCA circuit breakers. WBEM EventID: 653. WBEM ProviderName:
FPL_IndicationProvider.Warning7786
Cabinet Main Blower Failed. Probable Cause: Cabinet Blower Failed. Recommended
Action: Replace failed blower module as soon as possible following the Blower
Module Remove and Replace Procedures. WBEM EventID: 654. WBEM ProviderName:
FPL_IndicationProvider.Warning7791
48 Volt Converter Failed. Data Byte 3 specifies PDCA number. Probable Cause: The
48 Volt DC Converter powered by the PDCA identified failed in the named Bulk
Power Supply. Recommended Action: Contact HP Support personnel to troubleshoot
problem. WBEM EventID: 655. WBEM ProviderName: FPL_IndicationProvider.Warning7793
Fan failed in designated Bulk Power Supply. Probable Cause: Fan failure or fan
obstructed. Recommended Action: If fan is obstructed, remove obstruction. If no
obstruction, Contact HP Support personnel to troubleshoot problem. WBEM EventID:
657. WBEM ProviderName: FPL_IndicationProvider.Warning7795
1 Side Converter Over Temp. Probable Cause: If there are chassis codes indicating
an elevated ambient air temperature, other chassis codes will be generated and system
shutdown will be necessary. Recommended Action: Resolve the elevated ambient
air temperature problem as quickly as possible. If the air temperature gets too high,
the complex must be shutdown to avoid damage. WBEM EventID: 2436. WBEM
ProviderName: FPL_IndicationProvider.Warning7796
Bulk Power Supplies are not Redundant. Probable Cause: Entities were added to the
cabinet, increasing the estimated Power Consumption. Or, a non-functional GSP bus
entity has become functional, providing previously missing power consumption
information. Recommended Action: Purchase and install a Bulk Power Supply, if
redundancy is desired. WBEM EventID: 659. WBEM ProviderName:
FPL_IndicationProvider.Warning7798
+48V DC has exceeded its upper limit. Probable Cause: The cabinet's 48V power has
exceeded an acceptable upper threshold. Recommended Action: Contact HP Support
personnel to troubleshoot problem. WBEM EventID: 660. WBEM ProviderName:
FPL_IndicationProvError7799
+48V DC has fallen below its lower limit. Probable Cause: The cabinet's 48V power
has fallen below an acceptable lower threshold. Recommended Action: Contact HP
Support personnel to troubleshoot problem. WBEM EventID: 661. WBEM
ProviderName: FPL_IndicaError7803
Cabinet Fan Failed. Probable Cause: Cabinet Fan Failed. Recommended Action:
Replace failed cabinet fan module as soon as possible following the Cabinet Fan
Module Remove and Replace Procedures. WBEM EventID: 662. WBEM ProviderName:
FPL_IndicationProvider.Warning7806
Housekeeping power has exceeded expected levels. Probable Cause: The cabinet's
housekeeping power has risen above an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID:
670. WBEM ProviderName: FPL_IndicationProvider.Error7822
Housekeeping power has fallen below expected levels. Probable Cause: The cabinet's
housekeeping power has fallen below an acceptable upper threshold. Recommended
Action: Contact HP Support personnel to troubleshoot problem. WBEM EventID:
671. WBEM ProviderName: FPL_IndicationProvider.Error7823
The BPSs for the cabinet are illegally configured. Data Byte 3 = PDCA number.
Probable Cause: The BPS are installed in an illegal configuration. Recommended
Action: Re-configure the BPS in a manner consistent with the explanation in the
Problem Description statement. WBEM EventID: 672. WBEM ProviderName:
FPL_IndicationProvider.Warning7824
Platform Events 43