HP Insight Management WBEM Provider Events Reference Guide

Power could not turn on because CPUs in the system or SBL Domain are mismatched.
Probable Cause: The system/SBL domain has CPUs of different S/SPEC and/or a delta
greater than 1 in core stepping. Recommended Action: Determine which CPU part
number you want to keep, and remove those that don't match. DF from the CM>
menu will display S/SPEC and stepping to help identify mismatch. When the CPUs
all match try to power on again. WBEM EventID: 9903. WBEM ProviderName:
FPL_IndicationProvider.Error14483
The installed SBL is incompatible for the enclosure type, or blade bay. Probable Cause:
Each SBL2/SBL4 is constructed for the precise width of the enclosure bays. SBL2-7000,
SBL2E-7000, and SBL4-7000 are designed for the c7000 enclosure. SBL2-3000,
SBL2E-3000, and SBL4-3000 are designed for the c3000 enclosure. The SBL2-7000 and
SBL2-3000 must be installed with the monarch blade in bay 1, 3, 5, or 7. The
SBL2E-7000 and SBL2E-3000 must be installed with the monarch blade in bay 2, 4,
or 6. The SBL4 must be installed with the monarch blade in bay 1 or 5. This event is
being generated because the installed SBL does not match the environment.
Recommended Action: Change your installation to a supported configuration. WBEM
EventID: 9904. WBEM ProviderName: FPL_IndicationProvider.Error14485
Power on failed due to an SBL (Scalable Blade Link) mismatch. Probable Cause: Each
SBL2/SBL4 is constructed for the precise width of the enclosure bays. SBL2-7000,
SBL2E-7000, and SBL4-7000 are designed for the c7000 enclosure. SBL2-3000,
SBL2E-3000, and SBL4-3000 are designed for the c3000 enclosure. The SBL2-7000 and
SBL2-3000 must be installed with the monarch blade in bay 1, 3, 5, or 7. The
SBL2E-7000 and SBL2E-3000 must be installed with the monarch blade in bay 2, 4,
or 6. The SBL4 must be installed with the monarch blade in bay 1 or 5. This event is
being generated because the installed SBL does not match the environment.
Recommended Action: Change your installation to a supported configuration. Then
attempt power on again. WBEM EventID: 9905. WBEM ProviderName:
FPL_IndicationProvider.Error14486
Firmware on the system is mismatched. Probable Cause: One of the FW types within
the system has a mismatch across blades. Recommended Action: Use the SR command
from the CM> menu or look in the iLO web GUI to identify the mismatched FW and
bring it up to date with the rest of the system. WBEM EventID: 9906. WBEM
ProviderName: FPL_IndicationProvider.Error14487
Power failed to turn on due to mismatched firmware. Probable Cause: The revision
of one of the ROMs in the system does not match the revision of its counterparts.
One of the FW types within the system has a mismatch. Recommended Action: Use
the iLO SR command from the CM> menu or look in the iLO web GUI to identify
the mismatched FW and bring it up to date with the rest of the system. WBEM
EventID: 9907. WBEM ProviderName: FPL_IndicationProvider.Error14488
The primary system variables are uninitialized. Probable Cause: The primary system
variables are uninitialized. Recommended Action: The system variables must be
initialized. Please run SYSSET to initialize them. WBEM EventID: 9898. WBEM
ProviderName: FPL_IndicationProvider.Warning14495
The CPU power pod is no longer powering the CPU. Probable Cause: The CPU power
pod is no longer providing power to the CPU. It may not be plugged in to the sytem
board, or it may have failed. Recommended Action: If not plugged into the system
board, plug it in. Check that the connector is not loose. If not then you should replace
the FRU. WBEM EventID: 9908. WBEM ProviderName: FPL_IndicationProvider.Error14512
This blade has failed to show signs of boot. Probable Cause: Something has caused
the blade to fail to boot. No BOOT_START event was detected from this blade. Could
be the result of a corrupted SFW ROM, a failing processor, or a board failure of the
QPI link. Recommended Action: At the next convenient opportunity power cycle the
system power to all blades that are configured as part of a system with the failed
blade. Look for other errors that may have been logged. Reflash the SFW. WBEM
EventID: 9909. WBEM ProviderName: FPL_IndicationProvider.Error14516
ICH Mezzanine card is missing. Probable Cause: The communications to the ICH
MEZZ may have failed. Otherwise the ICH MEZZ is not present. Recommended
Action: The system will fail to power on if there is no ICH MEZZ on the monarch
blade. Please validate proper loading of the ICH MEZZ card if a pc on fails. WBEM
EventID: 9910. WBEM ProviderName: FPL_IndicationProvider.Warning14517