HP Integrity rx7640 and HP 9000 rp7440 Servers User Service Guide
Figure 59 Server Cabinet CRUs (Rear View)
Verifying Cell Board Insertion
Cell Board Extraction Levers
It is important that both extraction levers on the cell board be in the locked position. Both levers
must be locked for the cell board to power up and function properly.
Power to the cell board should only be removed using the MP:CM>PE command or by shutting
down the partition or server. Therefore, if the levers become unlocked, the partition will not have
a chance to logically shut down, and damage could occur to the operating system.
If the cell board is powered on and one lever becomes unlocked, the cell board will stay powered
on. However, if the cell board is powered off, it will not power on again until both levers are in
the locked position.
The lever status can be determined by issuing the MP:CM>DE command and viewing the power
status of the cell board controller (PDHC). The “ready” bit will only be true when both levers are
locked and all VRMs are installed. This status can be used to determine if both levers are locked
and the cell board is properly installed in the chassis. See Figure 60 (page 124) for a sample of
the output.
If the state is “RDY” denoted by capital letters in the computer output then the “ready bit” is true.
If the state is “rdy” as denoted by lower case letters in the computer output then the “ready bit”
is false. See Table 30 for details.
Verifying Cell Board Insertion 123