Event DescriptionEvent SeverityEvent ID
An electronic keying problem has been detected. Probable Cause: The 'e-keying error'
only occurs during the power-up if the SVB must be left off due to an electronic
keying problem. Recommended Action: Try installing SVB in a different location.Warning12399
A Blade was installed in an improper location in the enclosure in violation of enclosure
configuration rules. Review the installation documentation for additional information.
Check the OA for additional related events. Probable Cause: SVB inserted in an
improper location. Recommended Action: SVB must be installed in specific positions
relative to fans or other components. WBEM EventID: 7009. WBEM ProviderName:
FPL_IndicationProviderWarning12400
A Blade was installed in the enclosure in violation of enclosure cooling configuration
rules. Review the installation documentation for additional information. Check the
OA for additional related events. Probable Cause: The 'cooling error' occurs during
the power-up if the SVB must be left off due to insufficient cooling. Recommended
Action: More fans may be needed for sufficient cooling. WBEM EventID: 7010. WBEM
ProviderName: FPL_IndicationProviderWarning12401
The sx2000 fabric reported an unexpected error. Try reseating the cell that reported
the error. If assistance is required, notify the Call Center. Probable Cause: Firmware
internal data corruption. Recommended Action: Reset cell that emitted the event.
WBEM EventID: 7011. WBEM ProviderName: FPL_IndicationProviderWarning12403
The OA was unable to service a power-on request. Try re-issuing the power-on
request. If the problem reoccurs after subsequent requests, notify the Call Center for
assistance. Probable Cause: If Onboard Administrator is busy in processing another
requests, then it sends BUSY response for any requests that cannot be processed in
time. Recommended Action: Try issuing the requests after some time. If the problem
exists even after subsequent requests, please contact the HP representative. WBEM
EventID: 7013. WBEM ProviderName: FPL_IndicationProviderWarning12408
The IO backplane in the specified cabinet is reporting a non-redundant PCI power
condition. It is possible that one of the PCI bricks is not present or not functioning
properly. Check for PCI brick fault events. Probable Cause: One of the PCI bricks is
not present or not functioning properly Recommended Action: Check for PCI brick
fault events. WBEM EventID: 7014. WBEM ProviderName: FPL_IndicationProviderWarning12411
The migration source could not connect to the target. Probable Cause: The migration
source was unable to establish a network connection to the target. The guest will
continue to run on the source. Recommended Action: Check the network connection
between the source and target.Error12547
A migration has failed. Probable Cause: A migration has failed. The data indicates
a failure code. Recommended Action: Verify that the source and target network has
enough bandwidth and that the target has suficient resources.Error12548
A migration was not successful. Probable Cause: This message follows a
MIGRATION_ABORTED message. Recommended Action: None.Warning12550
The virtual machine was not able to allocate memory for an I/O device. Probable
Cause: Not enough memory is available. Recommended Action: Check the amount
of memory in use.Error12551
HP unsupported DIMM(s) has been detected on this partition. Probable Cause: HP
PFM service has detected one or more HP unsupported DIMMs on this partition.
Recommended Action: Make sure to have HP supported DIMMs installed.Warning12557
OS run-time critical shutdown occurred. Probable Cause: The OS has caused the
system to shut down. Recommended Action: Look at OS logs and crash data to
determine why the system shut down.Error12560
The amount of power expected to be drawn by the currently operating hardware is
greater than the rating of the currently operating Bulk Power Supplies (BPS). Probable
Cause: A bulk power supply has failed or was removed when the system had the
minimal number of required bulk power supplies. Recommended Action: Replace
the failed or removed bulk power supply. WBEM EventID: 7250. WBEM
ProviderName: FPL_IndicationProviderError12586