HP Integrity rx8620 Server User Service Guide

Removing the Side Cover
Figure 2-16 Side Cover Detail
To remove the side cover, follow these steps:
1. Connect to ground with a wrist strap.
2. Loosen the blue retaining screw securing the cover to the chassis. See Figure 2-16.
3. Slide the cover from the chassis toward the rear of the system.
4. Place the cover in a safe location.
Installing the Side Cover
To install the side cover, follow these steps:
1. Orient the cover according to its position on the chassis.
2. To properly seat the cover, slide the cover into position using a slow, firm pressure.
3. Tighten the blue retaining screw securing the cover to the chassis.
Power Distribution Unit
The server may ship with a power distribution unit (PDU). There are two 60 A PDUs available
for the server. Each PDU is mounted horizontally between the rear columns of the server cabinet.
The 60 A PDUs are delivered with an IEC-309 60A plug.
The 60A NEMA
2
PDU has four 20A circuit breakers and is constructed for North American use.
Each of the four circuit breakers has two IEC
3
-320 C19 outlets providing a total of eight IEC-320
C19 outlets.
The 60A IEC PDU has four 16A circuit breakers and is constructed for International use. Each
of the four circuit breakers has two IEC-320 C19 outlets providing a total of eight IEC-320 C19
outlets.
Each PDU is 3U high and is rack-mounted in the server cabinet.
2. NEMA — National Electrical Manufacturers Association
3. IEC — International Electrotechnical Commission
Power Distribution Unit 47