HP Integrity rx8640, HP 9000 rp8440 Server User Service Guide
Table 40 Typical HP 9000 rp8440 Server Configurations
Typical
Cooling
Typical
Power
Bulk Power
Supplies
Core
I/O
Hard Disk
Drives
DVDsPCI Cards
(assumes 10W
each)
Memory
per Cell
Board
Cell
Board
BTU/hrWattsQtyQtyQtyQtyQtyGBytesQty
129363789624216324
120623533624216164
1135233256220884
92252702424216322
8241241442208162
802323504220882
646318933110881
The air-conditioning data in Table 40 are derived using the following equations:
• Watts x (0.860) = kcal/hour
• Watts x (3.414) = Btu/hour
• BTU/hour divided by 12,000 = tons of refrigeration required
NOTE: When determining power requirements, you must consider any peripheral equipment
that will be installed during initial installation or as a later update. See the applicable documentation
for such devices to determine the power and air-conditioning that is required to support these
devices.
Boot Console Handler (BCH) for the HP 9000 rp8440 Server
The following section describes the boot console handler (BCH) for the HP 9000 rp8440 server.
Booting an HP 9000 sx2000 Server to BCH
After you power on the server or use the management processor (MP) bo command to boot an
nPartition past boot-is-blocked (BIB), the nPartition console will show activity while the firmware is
initialized and will stop at the BCH Main Menu (the Main Menu: enter command or menu>
prompt).
Use the BCH di command to display the current menu and its available commands.
Main Menu: Enter command or menu > di
---- Main Menu --------------------------------------------------------------
Command Description
------- -----------
BOot [PRI|HAA|ALT|<path>] Boot from specified path
PAth [PRI|HAA|ALT] [<path>] Display or modify a path
SEArch [ALL|<cell>|<path>] Search for boot devices
ScRoll [ON|OFF] Display or change scrolling capability
COnfiguration menu Displays or sets boot values
INformation menu Displays hardware information
SERvice menu Displays service commands
DIsplay Redisplay the current menu
HElp [<menu>|<command>] Display help for menu or command
REBOOT Restart Partiton
RECONFIGRESET Reset to allow Reconfig Complex Profile
----
Main Menu: Enter command or menu >
Boot Console Handler (BCH) for the HP 9000 rp8440 Server 159