Installation Guide, Third Edition - HP Integrity rx8640 SEU
NOTE: The term REO on the REO Cable Instructions label has the same meaning as the
term SBA.
5. Snap each cable under the cable clamps provided on the chassis frame. For cable to cable
clamp positioning, refer to Figure 2-14 (page 43).
6. Push the cable on the connector and secure the cable attached to the shroud by tightening
the captive screw attached to the cable.
7. Complete the procedure by securing the remaining three E-link cables in place with the
captive screw located on each cable.
See Figure 2-12 for E-link cable orientation.
Figure 2-12 E-link Cable Orientation on Server
Connecting E-link Cables to the SEU
1. Remove the top and left side covers from the SEU.
2. Remove the E-link cable bridge bracket, hold-down bracket, and filler plates at the rear of
the SEU in the upper right corner. Discard the parts just removed from the SEU.
3. Route the cable bundle up to the SEU and then inside the chassis.
4. Insert the cable assembly bracket tab into the corresponding slot in the chassis.
5. Screw the cable assembly bracket attached to the cable bundle into the chassis.
6. Route cables along the outside of the system backplane and match the cables to the connectors
using the REO Cable Instructions label affixed to the chassis.
NOTE: The term REO on the REO Cable Instructions label has the same meaning as the
term SBA.
7. Push the cable onto the connector and tighten the screw for each cable to secure the cable
in place to the backplane.