User Service Guide, Fifth Edition - HP Integrity rx8640 SEU

2 Server Site Preparation
This chapter describes the basic configuration, physical specifications and requirements for the
server.
Dimensions and Weights
This section provides dimensions and weights of the Server Expansion Unit components.
Table 2-1 SEU Dimensions and Weights
PackagedStandalone
28.0 (71.1)15.8 (40.0)Height—Inches (centimeters)
28.38 (72.1)17.5 (44.5)Width—Inches (centimeters)
35.75 (90.8)30.0 (76.2)Depth—Inches (centimeters)
210.6 (95.53)165 (74.8)Weight
1
—Pounds (kilograms)
1 Shipping box, pallet, and container adds approximately 45.6 lb to the total system weight when shipped. The size
and number of miscellaneous pallets will be determined by the equipment ordered by the customer.
Table 2-2 SEU Component Weights
Weight (lb/kg.)DescriptionQuantity
77.0 (34.93)Value added chassis1
3.7 (1.68)System backplane1
20.4 (9.25)PCI-X card cage assembly1
5.0 (2.27) eachPCI- X power supply2
12.0 (5.44) eachBulk power supply2
1.0 (0.45)Mass storage backplane1
6.3 (2.86)Core I/O backplane assembly (the module
core I/O cards slide into)
1
1.6 (0.73) eachHard disk drive1–4
2.2 (1.0) eachRemovable media disk drive1–2
Electrical Specifications
This section provides electrical specifications for the SEU.
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to
all cabinets.
Install a protective earthing (PE) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor described is to be connected from the unit to the building
installation earth or, if supplied by a separately derived system, at the supply transformer or
motor-generator set grounding point.
Dimensions and Weights 27