HP Integrity Superdome 2 User Service Guide
Rack specifications
Table 4 Compute enclosure weights
Static load
Dynamic load
(gross)DepthWidthU height
Total cabinet
area with
Rack
packing
materials
(HxDxW)
1,360.8 kg
(3,000 lb)
907.2 kg
(2,000 lb)
1,000 mm
(47.2 in)
600 mm (23.8
in)
42U219 x 121.92
x 90.3 cm
HP 10642 G2
(86.22 x 48 x
35.56 in)
907.2 kg
(2,000 lb)
689.5 kg
(1,520 lb)
1,000 mm
(39.4 in)
600 mm (23.8
in)
36U191.14 x
121.92 x
HP 10636 G2
36U 600 mm
81.28 cm(23.6 in)
Universal Rack (75.25 x 48 x
32 in
1,360.8 kg
(3,000 lb)
1,134 kg
(2,500 lb)
1,200 mm
(47.2 in)
600 mm (23.8
in)
42U218.44 x
147.06 x
HP 10642 G2
42U 600 mm
90.42 cm (86(23.8 in)
1200mm Rack x 57.90 x
35.60 in)
1,360.8 kg
(3,000 lb)
1,134 kg
(2,500 lb)
1,085.63 mm
(42.74 in)
597.8 mm
(23.54 in)
42U246.80 x
129.20 x 90
HP 642
1075mm
Intelligent Rack cm (85.35 x
50.87 x 35.43
in)
1,360.78 kg
(3,000 lb)
1,460.11kg
(3,219 lb)
1,300.2 mm
(51.19 in)
597.8 mm
(23.54 in)
42U85.82 x 57.87
x 35.43 in
HP 642
1200mm
(218.00 xShock
Intelligent Rack 147.00 x 90
cm)
IMPORTANT: Racks in the same complex must be the same height and depth.
Internal and external site door requirements for G2 racks
Internal site doorways must obey the following height requirements:
• For a 1m deep, 42U tall rack — no less than 2004 mm (78.8 in) in height.
• For a 1200mm deep, 42U rack — no less than 2007 mm (79.01 in) in height.
External doorways should not be less than 2215mm (87.20 in) in height to account for the lifted
height of the pallet.
Internal and external site door requirements for Intelligent Series racks
Internal site doorways must obey the following height requirements:
• For the 642 1075 — no less than 200.19 cm (78.816 in)
• For the 642 1200 — no less than 200.66 cm (79.00 in)
External doorways should not be less than 216.80 cm (85.35 in) for the 642 1075, and 215.00
cm (84.65 in) for the 642 1200 to account for the lifted height of the pallet.
22 System specifications