Table 8 Compute enclosure 3-phase HP 2400 W power supply specifications (North America/Japan)
(continued)
ValueSpecification
3.0m (10ft)
24.0 A at 200 VACMax input current per line cord
23.1 A at 208 VAC
Input requirements
200 VAC to 240 VAC line-to-line 3–phaseRated input voltage
50–60 HzRated input frequency
100 A for 10 msMaximum inrush current
3.5 mAGround leakage current
0.98Power factor correction
Table 9 Compute enclosure 3-phase HP 2400 W power supply specifications (International)
ValueSpecification
IEC-309 220–240V, 5–pin, 16 APower cords (4)
3.0m (10ft)
12.1 A at 220 VACMax input current per line cord
11.1 A at 240 VAC
Input requirements
200 VAC to 240 VAC line-to-neutral 3–phaseRated input voltage
50-60 HzRated input frequency
100 A for 10 msMaximum inrush current
3.5 mAGround leakage current
0.98Power factor correction
Table 10 Compute enclosure power requirements
VAWattsPower required (50–60 Hz)
90008820User expected maximum power
1
1
Typical maximum Power or User expected maximum power (Input power at the ac input expressed in Watts and Volt-Amps.)
This figure was developed with the absolute maximum configuration running applications designed to draw the maximum
power possible. It is highly unlikely that any real-world application will result in this amount of power use for any significant
time period.