HP Integrity Superdome 2 User Service Guide

Table 11 Compute enclosure PDU power options
Number of power
cords required (per
Power receptacle
requiredPlug or connector type
Source voltage
(nominal)Source/Circuit type
enclosure leaving the
rack)
2IEC 309 60A 3-Pole,
4 wire, Blue
IEC 309 60A 3-Pole,
4 wire, Blue, 3.6m
(11.8ft) power cord
200–220 VAC
line-to-line
(phase-to-phase),
3–phase
3–phase 60A
50Hz/60Hz
2IEC 309 32A 4-Pole,
5 wire, Red
IEC 309 32A 4-Pole,
5 wire, Red, 3.6m
(11.8ft) power cord
220 VAC to 240 VAC
line-to-neutral 3–phase
50Hz/60Hz
3–phase 32A
4IEC 309 63A Single
Phase, Blue
IEC 309 63A Single
Phase Blue , 3.6m
(11.8ft) power cord
200V to 240V ac
50Hz/60Hz
Single-phase 63A
6NEMA L6-30R Single
Phase
NEMA L6-30P Single
Phase, 3.6m (11.8ft)
power cord
200–240 VAC
50Hz/60Hz
Single-phase 30A
Table 12 IOX ac power specifications
ValueRequirements
200–240 VACNominal input voltage
50–60 HzFrequency range (minimum - maximum)
Single-phaseNumber of phases
3 ARated line current
30 A for 20msMaximum inrush current
0.97Power factor correction
1 mAGround leakage current
Table 13 IOX PDU power options
Number of power
cords required (per
Power receptacle
requiredPlug or connector type
Source voltage
(nominal)Source/Circuit type
enclosure leaving the
rack)
2NEMA L6-30R Single
Phase
NEMA L6-30P Single
Phase, 3.6m (11.8ft)
power cord
200-240 VAC
50Hz/60Hz
Single-phase 30A
2IEC 309 32A Single
Phase, Red
IEC 309 32A Single
Phase Red, 3.6m
(11.8ft) power cord
200-240 VAC
50Hz/60Hz
Single-phase 32A
Electrical specifications 25