HP mc-Series 5042 Rack Options Installation Guide
Automatic Door Release Kit 21
• With the half lock position, you partially attach the strike plates to the electromagnetic locks. This option
offers less resistance by only securing, not locking, the rear rack doors.
To install the rear electromagnetic locks:
1. Align the electromagnetic lock on top of the electromagnetic lock bracket, routing the magnetic lock
cable through the notch on the electromagnetic lock bracket.
2. Using the Allen wrench, insert and tighten two black cap screws to attach the electromagnetic lock to the
electromagnetic lock bracket on the top of the rear rack frame.
3. Install the electromagnetic lock assembly.
o To install the electromagnetic lock in the full lock position, align the electromagnetic lock assembly
to the sixth round hole from the right on the top of the rear rack frame. To attach the electromagnetic
lock assembly to the top of the rear rack frame, use a T-25 Torx screwdriver to insert and tighten the
two M5.5 self-tapping screws into the inner row of rack holes.
o To install the electromagnetic lock in the half lock position, align the electromagnetic lock assembly
to either the fifth or seventh round hole from the right on the top of the rear rack frame. To attach the