HP recommends that the water source for the HP MCS G2 be a dedicated chiller unit or
water-to-water heat exchanger that allows for line isolation, better control of individual systems,
and regulated water quality. The chilled water source for this loop would be provided by one or
more chiller systems. Advantages in using a dedicated loop include:
Easier scheduling of maintenance to either a building system or dedicated HP MCS G2 loop
Easier-to-maintain water quality parameters in the dedicated closed loop
Better temperature and flow regulation to guarantee the needs of the HP MCS G2
More flexibility to regulate water temperature in order to reduce the potential for condensation
Figure 16 depicts the HP MCS G2 being supplied directly by a dedicated chiller unit or
water-to-water heat exchanger in a closed loop configuration.
Figure 16: Dedicated chiller unit directly supplying the HP MCS G2
Plumbing considerations
A number of plumbing factors should be considered when installing the HP MCS G2:
Flow rate and pressure capacity of chilled water plant input to the design of the facility feed line
and dedicated water loop pipe diameters
Corrosion-resistant material within the piping system to reduce the potential for electrochemical
corrosion
Reduction of elbows and other restrictions that increase flow resistance
Insulation of piping to reduce risk of condensation and incidental heating of supplied chilled water
Availability of a floor drain or reclamation system to capture system condensation
Structural securing of piping to support weight of distribution network filled with water
Water quality management, including particulate filtration, treatment, and flushing provisions, with
isolation valves for service requirements