HP Modular Cooling System Generation 2 site preparation guide - Technical white paper
42
Another consideration for water is the required set point. Temperatures near or below 0°C (32°F)
mean that the chilled water plant condenser is very close to or below the freezing point of the water
(remember, the minimum chilled water temperature to be supplied to the HP MCS G2 is 7°C/45°F).
This could cause a blockage and damage to the unit, so an additive like glycol may be necessary to
lower the freezing point. However, the heat transfer potential of the water is lower, so proper
equipment capacity derating would need to taken into account.
In a cooling loop, metallic materials in a pipe distribution network are in constant contact with
recirculating liquid and can react with impurities to cause corrosion that can develop into leaks or
form deposits that can develop into blockages.
The rate of galvanic corrosion depends on the electrical potential between the two dissimilar metals
and the temperature of the liquid.
Note:
A 10°C rise in water temperature can double the rate of corrosion.
Additional water precautions
The following actions should be taken during the installation of the HP MCS G2:
Ensure that all foreign matter and particulates are flushed from the system prior to installing the
water kit for the HP MCS G2.
Evaluate the short- and long-term system requirements against available water capacity.
Ensure your chilled water loop is properly designed for liquid cooling systems and separate from
the sanitary water systems within your building (e.g., bathroom, sink, or drinking water).
Make sure facility managers understand that additional load is being added to the building’s
chilled water supply. Be aware that the heat load being added may have an effect on other
components being cooled by the chilled water plant.
Caution:
It is important that the water supply system feeding the HP MCS G2 is
capable of withstanding deadheading (operating with a closed line) and
rapid and frequent changes in flow requirements, including long periods of
time with zero water flow.
Plumbing materials to avoid
The following materials should not be used with a closed water system:
Oxidizing biocides
Aluminum components
High zinc/brass components
Non-stainless steel iron components