HP Modular Cooling System Generation 2 site preparation guide - Technical white paper
46
Item
Area/
condition
Yes
No
Comment/
date
Cooling considerations
24
Can the room temperature be maintained between the
recommended range of 20°C to 25°C (68°F to 77°F)
and allowable range of 15°C to 32°C (59°F to 90°F)
(up to 5,000 ft)? Derate 1°C/1,000 ft above 5,000 ft and up to 10,000 ft.
25
Can the humidity level be maintained at the recommended level of
40% to 50%, with allowable humidity levels of 20% to 60%?
26
Are air-conditioning filters installed/clean?
Water preparation considerations
27
Has the water been tested for acceptable quality for use in the
HP MCS G2 unit?
28
If the water quality is unacceptable, have adequate treatment and
filtration measures been put into place?
29
Have the water temperature and flow been evaluated?
30
If temperature and flow are not adequate, have supplemental chiller units
and water pumps been implemented to achieve ample performance?
31
Has an adequately sized water-to-water heat exchanger been implemented
to provide a dedicated water loop to the HP MCS G2 units?
32
Has piping of an appropriate diameter, material, and pressure tolerance
been installed to reach the back of each HP MCS G2?
33
Is there a provision for fluid collected from the condensation and overflow
hoses at each HP MCS G2 unit?