HP Modular Cooling System Site Preparation Guide

HP MCS Specifications
Physical Specifications
Table 2 lists the physical specifications of a single HP MCS and server cabinet as received from the
factory.
Table 2. HP MCS Physical Specifications
Parameter
Packaged system
(as shipped on pallet)
Unpackaged system
(off pallet, unwrapped)
Unpackaged
CTO system
Height 88.5 in. (2248 mm) 78.7 in (1999 mm) 78.7 in. (1999 mm)
Width 48 in. (1219 mm) 35.8 in. (909 mm) 35.8 in. (909 mm)
Depth 70 in. (1778 mm) 51 in. (1295 mm) 51 in. (1295 mm)
Weight 1310 lbs. (594 kg) [1] 1130 lbs. (513 kg) [2] 3330 lbs. (1510 kg) [3]
NOTES:
[1] Weight for a completely packaged system with unpopulated server rack.
[2] Weight for an unpackaged system with unpopulated server rack.
[3] Approximate weight for an unpackaged CTO system. Actual weight will vary according to configuration.
Electrical Specifications
Table 3 lists the electrical specifications for the HP MCS.
Table 3. HP MCS Electrical Specifications
Parameter Value Comments
Operating Voltage:
Minimum
Maximum
180 VAC
240 VAC
AC Line frequency 50/60 Hz
AC line phase Single
Rated input current 15 A Per line cord
Maximum inrush current 43 A Per line cord
Dropout/hold-up time at minimum line
voltage
20 ms
Circuit breaker rating LAHJ Per cord
Power factor < 0.7 At all loads
Ground leakage current < 3.0 mA Per line cord
Maximum power consumption
(HP MCS only)
2500 VA Varies according to rack load
220 V, 20 A NEMA L6-20-to-C19 (Qty 2) Power cords
240 V, 16 A IEC 309-to-C19 (Qty 2)
HP MCS Site Preparation Guide
11