Floor Loading
The computer room floor must be able to support the total weight of the installed server as well as
the weight of the HP MCS as they are moved into position. The information presented in this section
is directed toward raised floor installations.
NOTE:
HP cannot assume responsibility for determining the suitability of a
particular raised floor system. The customer or local agencies should
determine installation requirements. An appropriate structural engineer
should verify any floor system under consideration for a server
installation.
Raised floor loading is a function of the manufacturer’s load specification and the positioning of the
equipment relative to the raised floor grid. The following guidelines are recommended:
Some raised floor systems do not have grid stringers between floor stands. The lateral support for
the floor stands depends on adjacent panels being in place. To avoid compromising this type of
floor system while gaining under-floor access, remove only one floor panel at a time.
Larger floor grids (bigger panels) are generally rated for lighter loads.
Table 4 can be used to calculate the weight load of each HP MCS unit, including installed
equipment for proper floor planning.
Table 4. HP MCS weight calculation
Component Unit Weight
Qty.
(Multiply by) Total weight
HP MCS
(with unpopulated server rack)
1190 lbs. (540 kg) 1 1190 lbs. (540 kg)
Component #1: HP 9000 rp8420 322 lbs (146 kg) 2 644 lbs. (292 kg)
Component #2:
Component #3:
Component #4:
Rack total:
NOTE: Text in blue Included as an example.
NOTE:
The HP MCS has not been certified for seismic environments.