HP Modular Cooling System Site Preparation Guide

Electrical Considerations
The HP MCS provides two C20-type AC input connections and ships with two sets of power cords
for connecting to redundant AC power busses, if available. Only one power cord is necessary for
operation. The second cord can be connected to a redundant AC power bus to improve system
availability by protecting against power source failures or accidentally tripped circuit breakers.
NOTE;
Electrical practices and suggestions in this guide are based on North
American practices. For regions and areas outside North America, local
electrical codes will take precedence over North American electrical
codes. An example would be the recommendation that the protective
ground conductor be green with yellow stripes. This requirement is a
North American directive and does not override the local code
requirements for a region or areas outside North America
NOTE:
The power requirements discussed in this guide for the fans and
electronics for the HP MCS only. Data processing components such as
servers, storage and network devices must be considered separately
based on their individual power requirements.
System Grounding
HP server systems require two methods of grounding: power distribution grounding for safety, and
high-frequency signal grounding for equipment performance. Power distribution grounding involves
the main building electrical service entrance, electrical conduit, facility power panels, and
equipment cabinets (including the HP MCS and server cabinets), which should be grounded using
green/yellow insulated wire conductors according to the applicable electrical codes. High-
frequency grounding consists of using ground return conductors for intra- and inter-cabinet signal
interconnects as well as chassis and cabinet grounding.
For HP MCS and server systems installed on a raised floor, the floor assembly should be electrically
grounded to form a complete ground grid. An optimum raised-floor grounding solution is shown in
Figure 9.