HP Modular Cooling System Site Preparation Guide

Item Description
Specifications
8 System Drain Valve
Type: ¾-inch two-piece, full-port, brass ball valve with chrome plated brass ball, PTFE seats,
steel handle, with solder end connections.
Pressure rating: 600psi WOG, 150psi WSP.
Centerline elevation: 6 inches minimum above base floor.
Orientation: Stem vertical up for lateral level operation.
Watts® FBVS-3C or equivalent, typical 1
9 Hose Adapter Type: ¾-inch brass hose thread adapter, typical 1.
10 Hose Cap Type: ¾-inch brass hose cap, typical 1.
11 Fitting
Type: 1 ¼-inch male fitting from water kit supplied by Hewlett-Packard and installed by
plumbing contractor, typical 1.
NOTE: Follow critical tightening instructions supplied with fitting.
12 Hose
Type: 1 ¼-inch flexible hose supplied with HP Modular Cooling System (MCS). Hewlett-
Packard will make final connections, typical 2 connections
13 Condensate Line Pipe: ¾-inch copper or Schedule 40 PVC
Fittings: Wrought Copper or Schedule 40 PVC
Orientation: Sloping downward and away from MCS for gravity drain
14 Compression Fitting
Type: ¼-inch MPT X 6MM compression fitting, Parker Hannifin, FPB6-1/4 Prestolok fitting or
equivalent
15 Hose Barb
Type: ½-inch I.D. hose barb x ¾-inch MPT, Parker Hannifin, 125HBL-8-12, fitting or
equivalent
16 Hose
Type: 6mm outer-diameter (O.D.) flexible hose supplied with HP Modular Cooling System
(MCS). Hewlett-Packard will make final connection, typical 1 connection.
17 Hose
Type: ½-inch inner diameter flexible hose supplied with HP Modular Cooling System (MCS).
Hewlett-Packard will make final connection, typical 1 connection
18 Filter
1µm filter is recommended for optimal long-term performance of the MCS. A cartridge or bag
filter could be used in a full flow or side stream flow configuration.
General Plumbing Installation Guidelines
Contractors shall install all valves, strainers, and other piping components to the specifications
provided in the Chapter 3 section “
Piping approaches.” All components shall be readily
accessible.
Contractor shall furnish and install adequate piping supports to withstand 40 pounds of axial
and torsional force applied to piping by MCS chilled water hoses.
Contractor shall flush all lines of debris and cap prior to MCS installation.
Contractors shall furnish and install Armacell AP/Armaflex® closed-cell elastomeric thermal
insulation with minimum 1inch (25 mm) minimum wall thickness on all customer piping and
fittings. Contractors shall furnish and install similar insulation type with minimum ¼-inch (6.4 mm)
wall thickness for HP MCS chilled water hoses and fittings. The HP MCS hoses have a 1¾-inch
outer diameter (45 mm) and fittings have a 2½-inch outer diameter (64 mm) at the largest point.
All insulation joints shall be taped with AP/Armaflex® Insulation Tape, 1/8-inch (3mm) thick x 2
inches (50 mm) wide x 30 feet (9.1 m) long. Mitered fittings should be cemented with Armaflex®
520 Adhesive.
HP MCS Site Preparation Guide
28