HP Modular Cooling System Site Preparation Guide
Environmental Considerations
Table 11 lists the recommended environmental specifications for the HP MCS.
Table 11. Recommended Environmental Specifications
Parameter Value
Room Temperature (see note)
Recommended Minimum / Maximum
Allowable Minimum / Maximum
68° F (20° C) / 77° F (25° C)
59° F (15° C) / 90° F (32° C)
Humidity:
Recommended range
Allowable range
40% - 50%
20% - 60%
NOTE: The temperatures stated are for an elevation of 0 to 5,000 feet above sea level. The maximum operating
temperatures must be de-rated by 1° C per 1,000 feet for locations 5,000 to 10,000 feet above sea level.
HP MCS Site Preparation Guide
37